Chapter 5: Controller Settings
Testing the LED probes with blink mode
The blink mode will allow you to perform a visual test of the LED temperature probes.
1. On the controller, push either the
Up
or
Down
button until the
Temperature Probe Menu
appears,
then push the
Enter
button.
2. Push the
Up
or
Down
button until
Blink Mode Submenu
appears, hen push the
Enter
button.
3. Push the
Up
or
Down
button to select Probe 1 or Probe 2, then push
Enter
to select the probe you
want to test.
NOTE:
Probe 2 will only blink if it is currently in a mode that supports a second probe and it is
enabled.
The light on the selected temperature probe should begin to blink to visually let you know where the
temperature probe is located.
4. Select
Exit
and
Enter
to exit.
Figure 5-8
Blink Mode Menu
Pneg-2092
VariFlame Heater with Edge Connect
51
Содержание AP Cumberland VariFlame VF-16-ENG
Страница 19: ...Chapter 3 System Overview Figure 3 1 User Interface Flow Chart Pneg 2092 VariFlame Heater with Edge Connect 19...
Страница 20: ...Chapter 3 System Overview Figure 3 2 User Interface Flow Chart 20 Pneg 2092 VariFlame Heater with Edge Connect...
Страница 37: ...Chapter 4 Installation Figure 4 7 VariFlame EDGE wiring diagram Pneg 2092 VariFlame Heater with Edge Connect 37...
Страница 38: ...Chapter 4 Installation Figure 4 8 VariFlame EDGE schematic 38 Pneg 2092 VariFlame Heater with Edge Connect...
Страница 39: ...Chapter 4 Installation Figure 4 9 VariFlame EDGE mode wiring Pneg 2092 VariFlame Heater with Edge Connect 39...
Страница 40: ...Chapter 4 Installation Figure 4 10 Dipswitches 40 Pneg 2092 VariFlame Heater with Edge Connect...
Страница 56: ...NOTES 56 Pneg 2092 VariFlame Heater with Edge Connect...