AGA Shawbury Скачать руководство пользователя страница 5

4

If there is another appliance using air fitted in the
same or adjacent room, it will be necessary to pro-
vide an additional air supply.  

All materials used in the manufacture of air vents
should be such that the vent is dimensionally stable,
corrosion resistant, and no provision for closure.  Air
inlet grills should be positioned so they do not
become liable to blockage.  The effective free area
of any vent should be ascertained before installa-
tion. The effect of any grills should be allowed for
when determining the effective free area of any vent.  

Air vents direct to the outside of the building should
be located so that any air current produced will not
pass through normally occupied areas of the room.

An air vent outside the building should not be locat-
ed less than the dimensions specified within the
Building Regulations and B.S. 8303: Part 1 from any
part of any flue terminal. These air vents must also
be satisfactorily fire proofed as per Building
Regulations and B.S. 8303: Part 1.

Air vents in internal walls should not communicate
with bedrooms, bedsits, toilets, bathrooms or rooms
containing a shower.

Air vents traversing cavity walls should include a
continuous duct across the cavity. The duct should
be installed in such a manner as not to impair the
weather resistance of the cavity.

Joints between air vents and outside walls should be
sealed to prevent the ingress of moisture. Existing
air vents should be of the correct size and unob-
structed for the appliance in use. If there is an
extraction fan fitted in adjacent rooms where this
appliance is fitted, additional air vents may be
required to alleviate the possibility of spillage of
products of combustion from the appliance/flue
while the fan is in operation. Refer to B.S. 8303 Part
1.

Where such an installation exists, a test for spillage
should be made with the fan or fans and other 
appliances using air in operation at full rate, (i.e.
extraction fans, tumble dryers) with all external
doors and windows closed.

If spillage occurs following the above operation, an
additional air vent of sufficient size to prevent this
occurrence should be installed.

Note:- 

If there is any work that is being carried out

that would effect the air quality supplied to the stove
such as sanding a floor or glueing linoleum etc. the
stove must be out of operation.  The dust or vapours
may be a potential hazard, the air supply and local
area needs to be thoroughly ventilated before
putting the stove in operation again.

COMMISSIONING & HANDOVER

On completion of the installation allow a suitable
period of time for any fire cement and mortar to dry
out, when a small fire may be lit and checked to
ensure the smoke and fumes are taken from the
stove up the chimney and emitted safely to the
atmosphere. 

Do not run at full output for at least

24 hours.

On completion of the installation and commissioning
ensure that the operating instructions for the stove
are left with the customer. Ensure to advise the cus-
tomer on the correct use of the appliance with the
fuels likely to be used on the stove and warn them to
use only the recommended fuels for the stove.

Advise the user what to do should smoke or fumes
be emitted from the stove. The customer should be
warned to use a fire guard to BS 8423:2002 in the
presence of children, aged and/or infirm persons.

LOCATION

There are several conditions to be considered in
selecting a location for your stove.

A. Allowances for proper clearances to 

combustibles of the stove and flue pipes.

B.  The product must be installed on a non 

combustible hearth with adequate load bearing 
capacity.

C. Fluing considerations;  length of flue, length of 

horizontal run, flue termination.

D. Location within area to be heated.

FLOOR PROTECTION

It is recommended that this appliance is installed on
a solid, level, concrete base, a non combustible
hearth conforming to current Building Regulations
must extend to the front of the appliance. 

Содержание Shawbury

Страница 1: ...irm persons should be supervised at all times and should not be allowed to touch the hot working surfaces while in use or until the appliance has thoroughly cooled When using the stove in situations w...

Страница 2: ...rance to Combustibles 5 12 Safe Distance from Chimneys from Flammable materials 5 13 Stove Dimensions 6 14 Technical Data 6 15 Air Controls 7 16 Recommended Fuels 7 17 Refuelling 7 Refuelling onto a l...

Страница 3: ...is installed by a Competent Person registered with a Government approved Competent Persons Scheme HETAS Ltd operate such a Scheme and a listing of their Registered Competent Persons can be found on t...

Страница 4: ...ee elbows use 2 x 45o bends instead Horizontal runs of flue pipe should be avoided where it is unavoidable the maximum permitted horizontal run is 150mm The chimney flue must have the necessary cleara...

Страница 5: ...d other appliances using air in operation at full rate i e extraction fans tumble dryers with all external doors and windows closed If spillage occurs following the above operation an additional air v...

Страница 6: ...are must be taken to ensure that there is no risk of ignit ing combustible material an uninsulated flue pipe must be installed at least with a clearance of three times the diameter of the flue pipe i...

Страница 7: ...th BS EN 13240 NOTE A suitable chimney minimum profile chimney draft tightness etc is a basic condition for the proper functioning of fireplace stoves See professional advice before installing the sto...

Страница 8: ...open position for approximately 3 minutes allowing the new refuel charge to establish combustion before adjusting the air control to the desired setting Refuelling on to a low fire bed If there is in...

Страница 9: ...room as the appliance If the alarm sounds unexpectedly follow the instructions given under Warning Note above The most common cause of fume emission is flue way or chimney blockage For your own safet...

Страница 10: ...la tively small to permit the refractory to set prop erly and to season the stove 1 Before lighting the stove ensure that any build up in the firebox has been removed and that the ashpan has been empt...

Страница 11: ...burning fuel If a build up of creosote occurs on the glass it may be due to draft conditions poor quality fuel or very slow burning for a long time Only clean glass when the stove is thoroughly coole...

Страница 12: ...11 EXPLODED VIEW...

Страница 13: ...A_0000_081 12 CSN_021103_M6X16 13 031_030_181 14 119A_0000_151 15 119A_0000_131 16 042A_0000_121 17 4901_000_008_23 18 CSN_022301_8X35 19 119A_2000_001 20 544_080_031 21 119A_0000_101 22 001A_0000_271...

Страница 14: ...13...

Страница 15: ...14...

Страница 16: ...AGA Station Road Ketley Telford Shropshire TF1 5AQ UK Rev 001 DP261114 N00642AXX 15...

Отзывы: