AGA LITTLE WENLOCK Скачать руководство пользователя страница 5

5

VENTILATION AND COMBUSTION AIR
REQUIREMENTS

This appliance is rated at less than 6kW.   The min-
imum effective air requirement is 5.5 cm

2

. If a

draught stabiliser is used then this increases to 23.5
cm

2

. When calculating combustion air requirements

for this appliance use the following equation:
550mm

2

per each kW of rated output above 5 kW

should be provided, where a flue draught stabiliser is
used the total free area shall be increased by
300mm

2

for each kW of rated output.  If there is

another appliance using air fitted in the same or
adjacent room, it will be necessary to provide an
additional air supply.  All materials used in the man-
ufacture of air vents should be such that the vent is
dimensionally stable, corrosion resistant, and no
provision for closure.  The effective free area of any
vent should be ascertained before installation. The
effect of any grills should be allowed for when deter-
mining the effective free area of any vent.

Air vents direct to the outside of the building should
be located so that any air current produced will not
pass through normally occupied areas of the room.
An air vent outside the building should not be  locat-
ed less than the dimensions specified within the
Building Regulations and B.S. 8303: Part 1 from any
part of any flue terminal. These air vents must also
be satisfactorily fire proofed as per Building
Regulations and B.S. 8303: Part 1.

Air vents in internal walls should not communicate
with bedrooms, bedsits, toilets, bathrooms or rooms
containing a shower.

Air vents traversing cavity walls should include a
continuous duct across the cavity. The duct should
be installed in such a manner as not to impair the
weather resistance of the cavity.

Joints between air vents and outside walls should be
sealed to prevent the ingress of moisture. Existing
air vents should be of the correct size and unob-
structed for the appliance in use. If there is an
extraction fan fitted in the room or adjacent rooms
where this appliance is fitted, additional air vents will
be required to alleviate the possibility of spillage of
products of combustion from the appliance/flue
while the fan is in operation. Refer to B.S. 8303 Part
1.  

Where such an installation exists, a test for spillage
should be made with the fan or fans and other appli-
ances using air in operation at full rate, (i.e.extrac-
tion fans, tumble dryers) with all external doors and
windows closed. 

If spillage occurs following the above operation, an
additional air vent of sufficient size to prevent this
occurrence should be installed.

LOCATION

There are several conditions to be considered in
selecting a location for your stove.

A. Position in the area to be heated - central loca-

tions are usually best.  If situated in an alcove, 
site as far forward as possible, to provide more 
heat to the room.

B. Allowances for proper clearances to com -

bustibles.

CLEARANCE TO COMBUSTIBLES

It is recommended that this appliance is sited next to
and on a non-combustible surface. A minimum all
round clearance of 100mm will allow air circulation
and not impede the performance of the stove. If it is
necessary to site the stove near to a combustible
surface a minimum clearance of 600mm must be
maintained.  The connector may pass through walls
or partitions constructed of combustible materials
provided the connector is either listed for wall pass-
through or is routed through a device listed for a wall
pass-through and is installed in accordance with the
conditions of the listing.  Any unexposed metal that
is used as part of a wall pass-through system is
exposed to flue gases shall be constructed of stain-
less steel or other equivalent material that will resist
corrosion, softening, or cracking from flue gas at
temperatures up to 982°C.

STOVE DIMENSIONS

FLOOR PROTECTION

It is recommended that this appliance is installed on
a solid, level, non combustible hearth conforming to
current Building Regulations. 

Fig.5

Note:

The dimensions stated are in millimeters 

and may be subject to a /- variation.

Содержание LITTLE WENLOCK

Страница 1: ...appliance is hot while in operation and retains its heat for a long period of time after use Children aged or infirm persons should be supervised at all times and should not be allowed to touch the ho...

Страница 2: ...ion 5 10 Clearance to Combustibles 5 11 Stove Dimensions 5 12 Floor Protection 5 13 Lighting 6 14 Primary Air Settings 6 15 Recommended Fuels 6 16 Outputs 6 17 Re Fuelling 6 18 Overnight Burning 6 19...

Страница 3: ...tours To minimise the wind effects the flue termination point should be located a minimum of 1000mm from the roof measured vertically and 2300mm measured horizontally Where this termination point does...

Страница 4: ...place using approved fire cement ensuring that no cement is blocking the flue passageway REAR FLUE EXIT Push the flue connector pipe not supplied into the flue spigot and cement into place using appr...

Страница 5: ...is an extraction fan fitted in the room or adjacent rooms where this appliance is fitted additional air vents will be required to alleviate the possibility of spillage of products of combustion from...

Страница 6: ...urning it anti clockwise as this will help to eliminate any smoke or fly ash resident in the com bustion chamber Add fuel to fire taking care not to overfill higher than the front firebars Close fire...

Страница 7: ...rning of damp or unseasoned fuel as this will result in tarring flue ways and chimney i e peat or timber 7 Allow adequate air ventilation to ensure plenty of air for combustion 8 Do not burn rubbish h...

Страница 8: ...paper on the hearth and then a few small sticks kindling or an approved firelighter 4 Ignite and close the door 5 Never use inflammable liquid i e gasoline petrol paraffin etc to start or freshen up...

Страница 9: ...of the firebricks Part No s 11 12 before chimney cleaning When inspecting a masonry chimney start at the cleanout door normally found at the base of the chimney or on the outside If your chimney does...

Страница 10: ...OT USE ABRASIVE PADS OR OVEN CLEANSERS CONTAINING CITRIC ACID ON ENAMELLED SURFACES ENSURE THAT THE CLEANSER MANUFACTUR ERS INSTRUCTIONS ARE ADHERED TO LITTLE WENLOCK SOLID FUEL STOVE EXPLODED VIEW 1...

Страница 11: ...11...

Страница 12: ...12 Aga Station Road Ketley Telford Shropshire TF1 5AQ UK Rev 004 DP 131108 N00397AXX...

Отзывы: