DESN 511052
Fig. 9
DESN 511053
AROUND THE HOUSE
UNDER THE CAR PORT, ETC.
16
Minimum siting dimensions for flue terminals
Position Spacing
Minimum
inch/mm
A Directly below an openable
window, air vent, or any other
ventilation opening
11
3
/
4
”/300
B Below gutter, drain/soil pipe
3”/75
C Below eaves
7
7
/
8
”/200
D Below a balcony or car port roof
7
7
/
8
”/200
E From vertical drain pipes and soil
pipes
5
7
/
8
”/150
F From internal or external corners
11
3
/
4
”/300
G Above adjacent ground or balcony
level
11
3
/
4
”/300
H From surface facing the terminal
23
5
/
8
”/600
I Facing terminals
47
1
/
4
”/1200
J From opening (door/window) in
car port into dwelling
47
1
/
4
”/1200
K Vertical from a terminal
59”/1500
L Horizontally from a terminal
11
3
/
4
”/300