The 5--kW through 10--kW circuit breaker heaters can be wired for
single--supply circuit only.
Table 1 – Accessory Heater Usage
ELECTRIC HEATER PART NUMBER
SIZES USED WITH
kW
INTERNAL CIRCUIT PROTECTION
EHK205B
18-37
5
Circuit Breaker
EHK208B
18-37
7.5
Circuit Breaker
EHK210B
18-37
10
Circuit Breaker
Table 2 – Minimum CFM
Fan Coil Unit Size
EHK2-05B
EHK2-08B
EHK2-10B
18, 19
325
350
375
24, 25
450
475
500
30, 31
575
600
625
36, 37
700
725
750
Heater
assembly
locations
Breaker box
locations
Unit sizes 18-25
Unit sizes 31-37
(Top View)
(Top View)
(Front View)
(Front View)
A13365
Fig. 1 -- Installation Locations for EHK2 Heaters
Ground
Lug
Field
Power
Wiring
Field
Ground
Wiring
ON
OFF
L1
L2
A00077
Fig. 2 -- 5--kW, 7.5--kW, 10--kW Circuit Breaker
and Disconnect Heaters
NOTE
:
Use UL--listed conduit and conduit connector for
connecting supply wire(s) to unit to obtain proper grounding. If
conduit connection uses reducing washers, a separate ground wire
must be used. Grounding may also be accomplished by using
grounding lugs provided in control box.
Ground Connections
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
According to NEC, ANSI/NFPA 70, and local codes, cabinet
must have an uninterrupted or unbroken ground to minimize
personal injury if an electrical fault should occur. The ground
may consist of electrical wire or metal conduit when installed
in accordance with existing electrical codes. (See
Ground/Conduit Note below.)
!
WARNING