Mounting
TankControl 10
23
6.5
Mounting the submersible probe
1
Spacer
2
Star
3
Pressure sensor
1.
Plug the star onto the pressure sensor. Note the position of the
ribs at the star.
2.
Use the spacer to screw the star to the pressure sensor.
3.
Insert the submersible probe into the tank from the top.
4.
At the cable gland, adjust the cable length of the probe cable in
such a way that the probe tip reaches the tank bottom. The
measuring hole of the submersible probe must not be immersed
in sludge that may be present at the tank bottom. Any volume of
liquid below the measuring hole of the submersible probe is not
detected by the pressure sensor.
6.6
Mounting additional submersible probe at the tank (optional-
ly available)
The differential alarm of the second submersible probe is used to de-
tect different liquid levels in communicating tanks. In the case of mul-
tiple tanks, the first submersible probe should be installed in the first
tank, the second submersible probe in the last tank.