26
Commissioning
EN
DA 10/12/14
6.2.8
Simulation - setting parameters
Minimum
Specify the starting point of the simulation.
Maximum
Specify the end point of the simulation.
Delta
Specify the increments of the simulation. The simulated value is
increased or decreased by this value.
Key
Function
"up"
Short keypress
The value increases by delta
- Stopping of infinite loop
"down"
Short keypress
The value decreases by delta
- Stopping of infinite loop
"up"
Long keypress >3 s
The value increases by delta with the specified
timestep (endless loop)
- Change of direction of the infinite loop
"down"
Long keypress >3 s
The value decreases by delta with the specified
timestep (endless loop)
- Change of direction of the infinite loop
6.2.9
Selecting the language
Verify that you are in display mode.
1. Press all 3 keys simultaneously.
2. Hold the keys down until the language you want is displayed.
3. Release the keys.