4.5 Use: setup mode
In the setup-mode the following parameters can be changed:
•
output voltage: 220 / 230 / 240 Vac
•
bypass: enable / disable (see 4.4.6)
•
P (Phase) - N (Neutral) reversal indication: enable / disable (see 4.4.12)
•
output frequency: 50 / 60 Hz
The setup mode can only be entered if the UPS is in ‘standby’ -mode: connected to a live wall outlet
and switched off (LED 'operation' blinks).
1
Press keypad 'O' and keep it pressed while pressing 'I' simultaneously. Release both buttons.
The setup sequence starts with the setup of the output voltage, indicated by a blinking LED
‘operation’.
2
Scroll through the four functions with keypad 'I', one of the LEDs ‘operation’, ‘on bypass’, ‘on
battery’ or ‘alarm’ will blink, indicating which function has been selected (see fig 4.5).
3
Toggle the setting of the selected function by pressing switch 'O'. The LEDs on the LEDbar
‘runtime capacity’ shows the setting.
4
Store the new settings and leave the setup mode: press keypad '1' and keep it pressed while
pressing '0' simultaneously. Release both buttons.
NOTE
The unit can be used as a frequency converter: the input frequency range is 45-66Hz, the
output frequency is selectable 50/60Hz. If the unit is used as a frequency converter, the
bypass function is no longer available. As a result an audible alarm will be generated
continuously (see 4.4.6). To avoid this, we advise to disable the bypass.
WARNING
Changing of the output frequency can cause severe damage of equipment connected to
the appliance outputs of the UPS: Be sure that the new frequency is suitable for the
connected equipment!
fig. 4.5: setup menu
output voltage
bypass
P-N rev. indication
output frequency
50 Hz
disabled
disabled
220 Vac
60 Hz
enabled
enabled
230 Vac
240 Vac
- LEDs