4.5  Use: setup mode 

 

In the setup-mode the following parameters can be changed: 

 

output voltage: 220 / 230 / 240 Vac 

 

bypass: enable / disable (see 4.4.6) 

 

P (Phase) - N (Neutral) reversal indication: enable / disable (see 4.4.12) 

 

output frequency: 50 / 60 Hz 

The setup mode can only be entered if the UPS is in ‘standby’ -mode: connected to a live wall outlet 
and switched off (LED 'operation' blinks). 
 

Press keypad 'O' and keep it pressed while pressing 'I' simultaneously. Release both buttons. 

 

The setup sequence starts with the setup of the output voltage, indicated by a blinking LED 
‘operation’. 

Scroll through the four functions with keypad 'I', one of the LEDs ‘operation’, ‘on bypass’, ‘on 
battery’ or ‘alarm’ will blink, indicating which function has been selected (see fig 4.5). 

Toggle the setting of the selected function by pressing switch 'O'. The LEDs on the LEDbar 
‘runtime capacity’ shows the setting. 

Store the new settings and leave the setup mode: press keypad '1' and keep it pressed while 
pressing '0' simultaneously. Release both buttons. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

NOTE 

The unit can be used as a frequency converter: the input frequency range is 45-66Hz, the 
output frequency is selectable 50/60Hz. If the unit is used as a frequency converter, the 
bypass function is no longer available. As a result an audible alarm will be generated 
continuously (see 4.4.6). To avoid this, we advise to disable the bypass. 

 

 

WARNING 

Changing of the output frequency can cause severe damage of equipment connected to 
the appliance outputs of the UPS: Be sure that the new frequency is suitable for the 
connected equipment! 

 

fig. 4.5:  setup menu 

output voltage 

bypass 

P-N rev. indication 

output frequency 

50 Hz 

disabled 

disabled 

220 Vac 

60 Hz 

enabled 

enabled 

230 Vac 

240 Vac 

- LEDs 

Содержание 1000 VA VH Series

Страница 1: ...User manual VH Series Uninterruptible Power Supply 700 1000 1500 2000 3000 VA...

Страница 2: ...ower of the VH Series UPS the rear panel of the UPS shows the model chapter 9 the ratings 3 2 Installation rules The UPS is intended to be used in normal domestic and office situations Protect the UPS...

Страница 3: ...ect the DC connector of the internal batteries 5 Assemble the front panel insert the two metal clamps at the rear of the panel into the holes at the right side of the UPS then click the front panel in...

Страница 4: ...max rating 10A To connect the loads to the UPS 700 VA 2 outlets 1000 1500 VA 4 outlets 2000 3000 VA 6 outlets 3a Appliance outlet max rating 16A VH Series 3000 VA only To connect a heavy load to the...

Страница 5: ...not exceed the VA output rating of the UPS This way you ensure that the UPS is able to supply the required output and prevent that an overload situation will happen 4 Using the output cords provided...

Страница 6: ...power fails and the internal batteries supply the required power until either they are depleted or mains power returns 6 LED alarm blinks in case of an alarm 7 LED bar runtime capacity the remaining a...

Страница 7: ...this function is activated the UPS will switch off during a mains failure when the load is less than 5 of the maximum load In this way unnecessary discharging of the batteries is avoided The unit will...

Страница 8: ...bypass 4 4 3 0 4 0 4 hi o On battery 4 4 4 0 4 0 4 lo Battery low 4 4 5 25 0 4 hi Bypass out of limits 4 4 6 0 4 0 4 lo Overload 4 4 7 0 4 4 hi Replace battery 4 4 8 0 4 0 4 lo General alarm 4 4 9 0 4...

Страница 9: ...panel required or if a UPS shutdown command is given by the computer Restart depends on the setting of the auto restart function if set on the UPS will automatically restart when the mains returns if...

Страница 10: ...ower failure Allow the UPS to recharge the batteries See also 4 6 4 4 9 General alarm General alarm comprises a group of alarms the buzzer behaviour indicates which alarm is active 1 2 secs General fa...

Страница 11: ...the setting of the selected function by pressing switch O The LEDs on the LEDbar runtime capacity shows the setting 4 Store the new settings and leave the setup mode press keypad 1 and keep it presse...

Страница 12: ...tery test A deep battery test to be initiated through the UPS software via the USB communication port checks the actual battery capacity in order to ensure accurate runtime prediction During a deep ba...

Страница 13: ...al alarm 1 3 Battery low 4 On bypass 5 Remote UPS shutdown RxD 6 GND 1 Active if the output voltage of the UPS is no longer guaranteed due to other circumstances than already indicated by pin 1 3 4 Th...

Страница 14: ...the same for all VH Series models NOTE During battery replacement the UPS will not be able to support the load if a mains failure occurs It is recommended to switch off the load before disconnecting...

Страница 15: ...lso 4 3 3 Line cord not connected Read 3 3 6 Connect line cord Dead wall socket outlet or mains voltage out of limits Contact qualified electrician Tripped Thermal Circuit Breaker See above UPS switch...

Отзывы: