background image

32

7.2 Other Malfunctions and Solutions (No display on LED wire controller)

Malfunctions

Observing

Reasons

Solution

Heat pump is

not running

LED wire controller
no display.

No power supply

Check cable and circuit
breaker if it is connected

LED wire controller.
displays the actual time.

Heat pump under standby
status

Startup heat pump to run.

LED wire controller
displays the actual
water temperature.

1. Water temperature is
reaching to setting value, HP
under constant temperature
status.
2. Heat pump just starts to
run.
3. Under defrosting.

1. Verify water temperature
setting.
2. Startup heat pump after a
few minutes.
3. LED wire controller should
display "Defrosting".

Water
temperature is
cooling when HP
runs under
heating mode

LED wire controller displays
actual water temperature
and no error code displays.

1. Choose the wrong mode.
2. Figures show defects.
3. Controller defect.

1. Adjust the mode to proper
running
2. Replace the defect LED wire
controller, and then check the
status after changing the
running mode, verifying the
water inlet and outlet
temperature.
3. Replace or repair the heat
pump unit

Short running

LED displays actual water
temperature, no error code
displays.

1. Fan NO running.
2. Air ventilation is not
enough.
3. Refrigerant is not enough.

1. Check the cable connections
between the motor and fan, if
necessary, it should be
replaced.
2. Check the location of heat
pump unit, and eliminate all
obstacles to make good air
ventilation.
3 Replace or repair the heat
pump unit.

water stains

Water stains on heat pump
unit.

1. Concreting.
2. Water leakage.

1. No action.
2. Check the titanium heat
exchanger carefully if it is any
defect.

Too much ice on
evaporator

Too much ice on
evaporator.

1. Check the location of heat
pump unit, and eliminate all
obstacles to make good air
ventilation.
2. Replace or repair the heat
pump unit.

Содержание Hydro-Pro Inverter 07

Страница 1: ...nverter 16 horizontal R32 7024519 Hydro Pro Heat pump ABS 230V Inverter type Inverter 19 horizontal R32 7024520 Hydro Pro Heat pump ABS 230V Inverter type Inverter 24 horizontal R32 7024521 Hydro Pro...

Страница 2: ...Automated Environmental Systems Ltd 1 Wimbledon Avenue Brandon IP27 0NZ 01842 819130 sales automatedenvironmentalsystems co uk Buy online www automatedenvironmentalsystems co uk...

Страница 3: ...e in emission prevention and recovery of fluorinated greenhouse gases and handling safety the relevant type and size of equipment Record keeping 1 Operators of equipment which is required to be checke...

Страница 4: ...bility for the damage caused with the people objects and of the errors due to the installation that disobey the manual guideline Any use that is without conformity at the origin of its manufacturing w...

Страница 5: ...7 2 4 6 Compressor type Inverter Compressor Voltage V 220 240V 50Hz 1PH Rated current A 5 5 7 9 10 0 11 8 Minimum fuse A 9 12 15 16 Advised pool volume with pool cover m 10 25 15 60 18 66 25 85 Advis...

Страница 6: ...e V 220 240V 50Hz or 60Hz 1PH 380V 50Hz or 60Hz 3PH 220 240V 50Hz or 60Hz 1PH 380V 50Hz or 60Hz 3PH Rated current A 14 0 17 7 6 9 21 0 8 2 Minimum fuse A 21 27 10 34 13 Advised pool volume with pool c...

Страница 7: ...10 2 Dimension mm Model Inverter 7 Model Inverter 11 14 16...

Страница 8: ...11 Model Inverter 19 Model Inverter 24 24T 29 29T...

Страница 9: ...city 3 Swimming pool filters The unit may be installed in virtually any outdoor location as long as the specified minimum distances to other objects are maintained see drawing below Please consult you...

Страница 10: ...ity pH is used it is essential to protect the heat pump against excessively high chemical concentrations which may corrode the heat exchanger For this reason equipment of this sort must always be fitt...

Страница 11: ...nd terminal block marked WATER PUMP is located next to the first one The filter pump switch 24V can be connected to the second terminal block here This allows the filter pump operation to be controlle...

Страница 12: ...ime delay The heat pump has a built in 3 minute start up delay to protect the circuitry and avoid excessive contact wear The unit will restart automatically after this time delay expires Even a brief...

Страница 13: ...essories Installation Anti vibration bases 1 Take out 4 Anti vibration bases 2 Put them one by one on the bottom of machine like the picture Draining jet 1 Install the draining jet under the bottom pa...

Страница 14: ...the two joints like the picture shows 3 Screw them onto the water Inlet outlet junction Cable wiring 1 Open the terminal cover 2 Fix the power supply wire on joints Water pump wiring 1 Open the termi...

Страница 15: ...18 5 Electrical Wiring 5 1 SWIMMING POOL HEAT PUMP WIRING DIADRAM Inverter 7 11 14 16 19...

Страница 16: ...19 5 2 SWIMMING POOL HEAT PUMP WIRING DIADRAM Inverter 24...

Страница 17: ...20 5 3 SWIMMING POOL HEAT PUMP WIRING DIADRAM Inverter 29...

Страница 18: ...y isolated from the rest of the unit Grounding the unit is still required to protect you against short circuits inside the unit Bonding is also required Disconnect A disconnect means circuit breaker f...

Страница 19: ...photo5 6 Display Controller Operation 6 1 The buttons of LED wire controller 6 2 The keys and their operations NOTE Every time when the heat pump connects to the power the LED display shows a code for...

Страница 20: ...r temperature Tset Current water in temperature Tset 2 Current working mode After 3 minutes or above it will switch to Tset eg 28 Tset 2 eg 30 Heating mode Cooling mode Tset eg 28 Tset 2 eg 26 Cooling...

Страница 21: ...st 0 1 0 1 Manual defrosting mode 0 Normal mode P1 Working mode 0 1 1 1 Heating mode 0 cooling mode P2 Timer on off 0 1 0 1 Timer on off is under function 0 Timer on off is out of function The setting...

Страница 22: ...light will be flash the heat pump will operate in Full output only 6 2 10 While you choose the Smart the heat pump will just operate in Small output Medium output and Full output When in Small output...

Страница 23: ...ck the wiring for water flow switch 2 Change the water flow switch 3 Check the water pump or the waterway system EE 04 Over heating protection for water temperature T2 in heating mode 1 Low water flow...

Страница 24: ...rd EE 11 IPM module protection 1 Data mistake 2 Wrong compressor phase connection 3 Compressor liquid and oil accumulation lead to the current becomes larger 4 Compressor or driver board damaged 1 Pro...

Страница 25: ...Fan blade is broken 4 The screw in the driver board is not tight 1 Change a new driver board 2 Check if the motor speed is too low or fan motor damaged change another one 3 Change another fan blade 4...

Страница 26: ...1 Re fix the wiring of the sensors 2 Change the sensor PP 04 Gas return sensor failure 1 The sensor failure or short circuit 2 The wiring of sensor is loose 1 Re fix the wiring of the sensors 2 Chang...

Страница 27: ...ple below Mode Water out temperature Setting temperature Condition Malfunction Heating mode 36 29 Tout Tset 7 EE04 Overheating protection for water temperature T2 Cooling mode 23 30 Tset Tout 7 PP11 T...

Страница 28: ...T1 27 last for 30 minutes Water pump will enter standby mode for 2 hours and will not start except turn off power supply and restart Heat pump will restart 3 minutes after the water pump exit the sta...

Страница 29: ...ose the wrong mode 2 Figures show defects 3 Controller defect 1 Adjust the mode to proper running 2 Replace the defect LED wire controller and then check the status after changing the running mode ver...

Страница 30: ...33 8 Exploded Diagram and Maintenance 8 1 Exploded Diagram Model Inverter 7...

Страница 31: ...34...

Страница 32: ...motor 45 Water inlet temp sensor clip 14 Left panel 46 Titanium heat exchanger 15 Fan blade 47 O ring 16 Front panel 48 Blue rubber ring 17 Controller box 49 Water connection 18 Ventilation grid 50 R...

Страница 33: ...36 Model Inverter 24...

Страница 34: ...37...

Страница 35: ...id reservoir to EEV 17 Bracket for panel 55 Pipe Filter to Liquid reservoir 18 Fan motor 56 Pipe EEV to Distribution 19 Fan blade 57 EEV 20 DC motor casing tube 58 Filter 21 Controller box 59 Pipe Tit...

Страница 36: ...as a result of the dirty of clogged filter 3 You should discharge the water from bottom of heat exchanger if HP unit will stop running for a long time specially during the winter season 4 In another...

Страница 37: ...he product with a flow rate outside the published minimum and maximum specifications 7 Use of components or accessories not designed or made for this product 8 Chemical contamination of the air used b...

Страница 38: ...hipping service of your choice 4 If you choose express shipment by a shipping service selected by you you are responsible for paying the shipping costs Return procedure 1 Before requesting an RMA numb...

Страница 39: ...MA number we will return all of the products at your expense 10 No return shipments at all will be accepted without an RMA number Absolutely no exceptions to this rule are allowed 11 An RMA number rem...

Отзывы: