OPERATING GUIDELINES 

Before filling the sump you should first check that the system is operating correctly:

1.  Switch the control panel to AUTO
2. 

Hold the STOP level floatswitch in the UP position (Nothing should happen)

3. 

Hold the START level floatswitch in the UP position (Pump should start)

4.  Lower the START level floatswitch (Pump should continue to run)

5. 

Lower the STOP level floatswitch (Pump should stop)

CAUTION:

 MANUAL OPERATION

The pump(s) can be set to run continuously by setting the control panel selector to manual. This  

setting is for maintenance and testing purposes only and should not be left on unattended. You should 

take care to ensure that the pumps aren’t allowed to run dry for any extended period of time. 

AUTOMATIC OPERATION 

The packaged pumping station has a fully automatic operation and once setup it should need no  

further adjustment. The working parts of the pumping chamber comprise of the pump(s), the level  

regulating float switches and control panel.

BEFORE SWITCHING ON

 

•  The float switches should be set at the levels shown in the installation instructions. The pump(s) 

should be fully lowered down the guiderails onto the base pedestal, or lowered to sit upright at the 

bottom of the tank if freestanding.  

•  The electrical supply should be checked that it is connected to the to the control panel, and that 

the cover is secured. 

SWITCHING ON 

•  Set the pump(s) operating switch on the front of the control panel to OFF, then switch on the  

electrical supply at the main isolating switch.  

• 

Turn the selector switch to AUTO (or ON). Providing sufficient water is in the chamber the pump 

should start. For twin pump systems only one of the pumps should run at a time.  

•  If there is insufficient water in the chamber the pump will not run.  

•  Allow water to enter the chamber until the START float switch is reached and fully tilted. The pump 

should now run.  

•  The pump will continue to run until sufficient water has left the chamber to allow the STOP float to 

hang vertically. Once this level has been reached the pump should stop.  

•  Once sufficient water has again flowed into the chamber, the above cycle will repeat. On twin pump 

systems the pumps will alternate each cycle to share the wear. 

© Automated Environmental Systems Ltd. February 2022

Содержание Baby Wipes

Страница 1: ...CE GUIDELINES Automated Environmental Systems Ltd Unit 1 1 Wimbledon Avenue Brandon Suffolk IP27 0NZ 01842 819130 service automatedenvironmentalsystems co uk Packaged Pumping Station Automated Environ...

Страница 2: ...PUMPING STATION IS DESIGNED TO HANDLE EFFLUENT The following items must be kept out of the pump chamber Baby Wipes Nappies Cleaning Wipes Sanitary Towels THESE TYPES OF PRODUCTS ARE LIKELY TO BLOCK TH...

Страница 3: ...the technologies applied to the equipment supplied Whilst every care has been taken during the compilation of this manual to ensure that the information provided is correct no liability can be accepte...

Страница 4: ...Confined Space Entry certification should enter a pump chamber and then only if there is a second qualified person equipped with required safety equipment supervising The following checklist although...

Страница 5: ...re is relieved DANGER HIGH VOLTAGE Control boxes contain high voltage live wiring and terminals Entry of control boxes is not permitted except by qualified electrical personnel only ensure controller...

Страница 6: ...site work the dangers of working with water and electricity pose severe threats to health if obvious and fundamental precautions are not taken Therefore if you are in any doubt to any of the following...

Страница 7: ...order to be protected from any external force the chamber should be completely surrounded by concrete The concrete surrounding the chamber should be of suitable thickness usually a minimum of 150mm an...

Страница 8: ...uld concrete be poured directly onto the chamber Attempting to pour too much concrete at once will result in the chamber floating or particularly above the halfway point damage to the chamber due to e...

Страница 9: ...out and all sand debris etc removed from the chamber If vehicular traffic will be passing over the chamber it is ESSENTIAL that the cover slab is constructed so that there is NO DIRECT LOAD on the ch...

Страница 10: ...separately for instance on projects where a separate turret is to be installed B Remove the upper bracket from top of turret A C Then position the other end of the rails down onto the guide s of the l...

Страница 11: ...the control panel inside the pumping station Allow enough slack for the adjustment of the float switches easy installation and removal of the pump s Ensure that all electrical cables are secured and...

Страница 12: ...s are to be connected using only two of the cable cores the colour coding can be found inside the instructions manual provided with the float s The core that isn t used should be cut off and isolated...

Страница 13: ...onger than halfway down the pump and below the inlet level The pump must not run dry before the float switch reaches its off position The alarm float switch needs to activate above the pumps float swi...

Страница 14: ...ld be set at the levels shown in the installation instructions The pump s should be fully lowered down the guiderails onto the base pedestal or lowered to sit upright at the bottom of the tank if free...

Страница 15: ...e pump s are checked every six to twelve months to ensure that the oil chamber is free from contamination as per the manufacturer s instructions and to check the pump s for any blockages and to clean...

Страница 16: ...or cloth Plastic objects Sand rock stones or other debris Failure to follow these guidelines may invalidate your warranty in which case any service visits and replacement pumps parts as a result of mi...

Отзывы: