Installation, Operation & Maintenance Manual
IM-875
19
Troubleshooting Guidelines
(cont.)
CHECK LIGHT
SYMPTOM
POSSIBLE CAUSE
BURNER
LOCKOUT
Burner Lockout
light
is Lit
1. If on
INITIAL START UP
of a newly installed system, the gas line may have air
trapped in it. Remove the test plug upstream of the safety shut off valve and bleed
the gas line to remove the air. It may require resetting the flame safeguard several
times.
2. If pilot does light as proven by the flame light on the flame safeguard, but does
not stay lit, adjust needle valve on pilot gas line. Close valve fully and open ½ turn
and retry. If pilot will not stay lit, open to 1 turn open.
3. Push burner reset button on flame safeguard or the burner reset button on
the remote panel. If burner continues to lock out, check for spark during ignition
process.
4. No ignition spark. Crack access door (or view pilot through view-port) and look at
the pilot side of the burner. You should be able to see the igniter sparking. (Spark is
present only when the pilot light is lit, this is only 10 sec.)
5. Spark plug fouled. If the spark is not visible, remove the spark plug and clean
it with a wire brush. Check the gap between ground electrode, it should be
approximately 3/32".
6. Ignition wire broken or grounded against unit.
7. Defective ignition transformer or spark plug. Disconnect the ignition wire from
the spark plug and thread it back through the hole on the control side of the unit.
Hold the wire by the insulated cover and place the spark plug electrode approx.
1/16" from a bare surface of the unit. Start the ignitions sequence; it should spark.
(REMEMBER TO RESET THE FLAME RELAY BEFORE DOING THIS.) If no spark is
observed, replace the ignition transformer.
8. Low pilot flame. Increase pilot gas pressure by adjusting pilot regulator.
9. Ultra-violet flame detector sight glass is obstructed. Check lens or sight tube for
moisture, dirt or insects. Clean or dry lens with a soft cloth.
DIRTY FILTER
Dirty Filter Light
is Lit
1. If the dirty filter light is
lit
, the filters are dirty to the point where the airflow is
reduced. Change or clean filters.