background image

29

accuracy.
The fan is driven in a proportional way except when a fixed speed is set 

FI1..FI3

. With fixed speed, the fan can be only turned off or turned on at 

the fixed speed; there is no proportional regulation, actually it becomes ON-
OFF regulation with relevant hysteresis set on parameter 

P19

.

The fan will be turned on only when the valve is open, in order to avoid the 
fan operation together with a closed valve.

Installer configuration

The ‘installer’ configuration is used to setup the controller in order to get 
the best regulation in conjunction with the type of heating/cooling system 
installed. In order to enter the configuration menu, turn off the controller, 
then keep depressed both buttons ‘

on/off

’ and ‘

menu

’ together for some 

seconds, until the word ‘

COn

’ (configuration) appears on the display. 

From this state on, each time the “menu” button is depressed a different 
parameter is displayed, identified with a ‘

P

’ followed by a number, i.e. 

from 

P01

 to 

P35

.

The end of configuration is indicated by the word ‘

End

’: if now the ‘menu’ 

button is depressed once again the configuration is saved in a non-volatile 
memory and the controller jumps into the normal operation mode. In case 
the ‘on/off’ button is depressed, at any time the controller exits from the 
configuration menu, without saving the changes. When parameters are 
examined, if the ‘speed’ button is depressed once, the actual value of the 
parameter is displayed.
When the value is shown press again the ‘speed’ button to change the 
value. Parameters from 

P01

 to 

P11

 can be set by pressing several times in 

sequence the ‘speed’ button until the desired value is reached.
The following parameters, being variable in a wider range, can be modified 
by first pressing once the ’speed’ button, so that the ‘modify parameter’ 
mode is entered, then turning the knob to modify the desired value. Upper 
and lower limits for the knob regulation are redefined each time according 
to the actual parameter allowable range. In order to disable the access 
to configuration menu to unauthorized users, an internal jumper, 

JP3

(shown in Fig. 3), can be removed; after this any attempt to enter in the 
configuration menu will result in an error message.

Configuration parameters explanation

All parameters used in the installer configuration are shown in Table 1 and 
explained in the following.

P01

: System type selection.

2 pipes system: when configured for a two-pipes system the controller 
drives one valve only, wired at the ‘heating’ output terminal, both when 
heating and when cooling, as the same valve is going to control either hot 
or cool water flow.
4 pipes system: when configured for a four-pipes system the controller 
drives both valves outputs in order to activate either hot or cooling water 
according to the actual requirements of the controlled environment.

P02

: This parameter sets the way the controller switches from the cooling 

mode (summer) to the heating mode (winter) and vice versa.
The switching can be either manual or automatic:
Manual: The user manually sets the heating or the cooling mode.
Automatic: The controller automatically selects the switching from the 
heating to the cooling mode or vice-versa.
This automatic operation is different according to the system type set 
with parameter 

P01

.

If the system is a 4-pipes one, the controller operates with neutral zone thus 
activating the heating or cooling according to the set-point temperature. In 
case of a 2-pipes system the controller operates a changeover according 
to the supply water temperature. When the supply water temperature is 
low (that is below the threshold set with parameter 

P23

) the controller 

switches to cooling mode.
On the opposite side, when this temperature is high (that is above the 
threshold set with parameter 

P24

) the controller switches to heating 

mode. In case the supply temperature is neither too low nor too high the 
operating mode is kept unchanged, but it still can be changed manually. 
When the supply water sensor is not installed or is not properly working 

ENGLISH

ESPAÑOL

DEUTSCH

ITALIANO

FRANÇAIS

Содержание WMT20

Страница 1: ...ND 0 10V OUTPUT THERMOSTAT MIT BILDSCHIRM FÜR FAN COIL MIT AUSGANG FÜR VENTILATOR 0 10V THERMOSTAT AVEC ECRAN POUR VENTILO CONVECTEURS ET SORTIE VENTILATEUR 0 10V TERMOSTATO CON DISPLAY PARA FAN COIL CON SALIDA VENTILADOR 0 10V WMT20 37040 Bevilacqua VR Italia Via Roma 996 1103 AWMT20UJ 6371600_04 ...

Страница 2: ...dukten und Dienstleistungen vorzunehmen Der Hersteller haftet für die Produktkonformität gemäß der Europäischen Richtlinie 1999 44 EG und dem Dokument zur Produktgarantiepolitik der Hersteller Auf Anfrage steht Ihnen beim Händler der ausführliche Produktgarantietext zur Verfügung GARANTÍA En la óptica de un continuo desarrollo de los propios productos el fabricante se reserva el derecho de aportar...

Страница 3: ...3 INSTALLAZIONE INSTALLATION AUFSTELLUNG INSTALLATION INSTALLACIÓN Fig 4 Abb 4 2 1 Fig 2 Abb 2 Fig 1 Abb 1 B B A JP1 JP2 JP3 14 12 13 9 8 2 7 6 5 4 3 Fig 3 Abb 3 ...

Страница 4: ...lador Bild 5 Verbindungsschema für die Steuerung der beiden Aktuatoren on off mit 230V pro Anlage mit 4 Rohren und proportionaler Steuerung SCHEMA DI COLLEGAMENTO WIRING DIAGRAM SCHALTSCHEMA SCHÉMA DE BRANCHEMENT ESQUEMA DE CONEXIÓN V FAN Uscita segnale 0 10V ventilatore 0 10V fan signal output Signalausgang 0 10V Ventilator Sortie signal 0 10V ventilateur Salida señal 0 10V ventilador SWI Sonda a...

Страница 5: ...nnected to the 230V Neutral through the motor drive In this case you cannot consider the 24V as a very low safety voltage hence it will be the installer s duty to grant a proper insulation aACHTUNG Im Falle einer Anspeisung des Thermostats von 24V kann man diese Niedrigspannung an den Neutralpunkt von 230V mithilfe der Betätigung des Motors anschließen In diesem Fall kann man bei 24V nicht mehr vo...

Страница 6: ... The fan proportional output is always turned off 0V when the valve output OUT COOL or OUT HEAT is off not shown on the scheme Le schéma montre le pilotage des vannes dans un système à 4 tuyaux avec zone neutre De façon analogue la sortie de la vanne chaude OUT HEAT d un système à 2 tuyaux sera pilotée de la même manière dans ce cas là la Ts température du point de consigne coïncidera avec la Ts r...

Страница 7: ... ON OFF válvula calor V FAN Uscita proporzionale ventilatore Fan proportional output Proportionaler Ausgang Ventilator Sortie proportionnelle du ventilateur Salida proporcional ventilador Ta Temperatura ambiente Ambient temperature Umgebungstemperatur Température ambiante Temperatura ambiente Ts Temperatura setpoint manopola Setpoint temperature knob Temperatur Setpoint Einstellgriff Température d...

Страница 8: ...8 Fig 8 2 BUUFOUJPO GPS 3 QJQF G 5BU ...

Страница 9: ...9 Fig 9 ...

Страница 10: ...10 Fig 10 ...

Страница 11: ...Normal When changing the readout the controller informs the user about the parameter shown according to the following table tA Room ambient temperature Set Set point temperature TP Supply pipe water temperature ECO Economy function Active When the button is depressed several times the display readout cycles across the above mentioned temperatures After a few inactivity seconds the display readout ...

Страница 12: ...stic cover pressing with the help of a tool like a screwdriver the plastic tooth located in the lower slot as indicated in Fig 1 raising at the same time the front cover as indicated in Fig 2 2 Unmount the plate fixed at the controller back by pressing the plastic tooth shown in A Fig 3 and at the same time pull the plate to the bottom until it becomes free from the plastic base 3 Fix the plate to ...

Страница 13: ...rtional output of the fan at terminal 9 and the reference earth at terminal 8 shall control the drive input as shown in figure 5 and 6 The input signal earth is often internally connected to the supply Neutral In this case it is possible not to connect the terminal 8 output signal earth because the earth is granted by the Neutral supply terminal take care this Neutral is connected to terminal 6 Sho...

Страница 14: ...e than one controller is not allowed All remote sensors bimetallic contact and window contact must have a galvanic insulation against earth as well as against the mains power In case precending two directions are not respected an irreversible product damage can follow All remote sensors bimetallic contact and window contact must be double insulation or reinforced insulation rated in case they are ...

Страница 15: ... sensor and can be displayed with 1 C resolution in the 0 99 C range In case the acquired temperature falls outside the operating range mentioned the display will show the letters Or out of range In case the sensor acts as an open circuit or a short circuit the display will show the letters EEE error and all functions related with this data are not performed In case the system doesn t require the ...

Страница 16: ...leaned In order to reset the warning and the relevant time counter once the cleaning has been made just keep depressed the speed button for at least 10 seconds until the regulator will confirm to have reset the warning by showing again the words FIL TER Temperature regulation This device can drive in a proportional way the fan speed in order to control room temperature with the highest comfort and ...

Страница 17: ...he actual parameter allowable range In order to disable the access to configuration menu to unauthorized users an internal jumper JP3 shown in Fig 3 can be removed after this any attempt to enter in the configuration menu will result in an error message Configuration parameters explanation All parameters used in the installer configuration are shown in Table 1 and explained in the following P01 System...

Страница 18: ... on P08 This parameter sets the type of sensor connected to the supply water temperature input at terminals 12 and 14 When set to value 0 or 1 a temperature sensor is expected for the acquisition of water temperature When 1 is set the temperature value is also shown over the display according to the user choice In case 0 is set the information coming from the temperature sensor is still used for t...

Страница 19: ... raised when in cooling mode by this step once the Economy function is made active When this is set at 0 0 the Economy function is actually disabled P19 This parameter defines the hysteresis in C with which the ON OFF outputs are controlled according to the ambient temperature variations P20 In case the controller is configured for a neutral zone operation this parameter determines the relevant ampl...

Страница 20: ... same duct for signal wires and power wires as the temperature reading accuracy could be impaired Wirings can be usefully made with bipolar screened cable whose screen is only wired at the regulator side terminal 14 with 1 5 mm minimum cross section and 15 m maximum length In the normal operation with internal sensor the controller conditions the signal acquired according an exclusive algorithm de...

Страница 21: ...lation 1 Valves only 2 Fan only 3 Valves and fan 0 P05 Heating output type 0 NC ON OFF valve 1 NA ON OFF valve 0 P06 Cooling output type 0 NC ON OFF valve 1 NA ON OFF valve 0 P07 Fan output type 0 Direct action 1 Reversed action 0 P08 Supply water sensor input 0 Do not show temperature 1 Show temperature 2 Bi metallic contact 3 Window contact 4 Reversed window contact 0 P09 De stratification 0 Neve...

Страница 22: ...2 Room temperature correction offset C 5 0 5 0 10 0 P13 Heating set point knob lower limit C 5 0 35 0 30 0 P14 Heating set point knob upper limit C 5 0 35 0 10 0 P15 Cooling set point knob lower limit C 5 0 35 0 30 0 P16 Cooling set point knob upper limit C 5 0 35 0 0 0 P17 Anti freeze threshold temperature C 0 0 15 0 0 0 P18 Economy reduction C 0 0 10 0 0 2 P19 Ambient temperature hysteresis C 0 ...

Отзывы: