The units are designed for installation in closed 

environments in 'urban’, non-marine atmos-

phere conditions that are not corrosive or dusty.

The following concentrations of the air polluting 

factors where the unit must operate must not 
be exceeded under any circumstances:

SO

2

< 0.02 ppm

H

2

S

< 0.02 ppm

NO,NO

2

< 1 ppm

NH

3

< 6 ppm

N

2

O

< 0.25 ppm

The unit must not be installed in areas char-

acterised by the presence of flammable gases 

or acidic or alkaline substances. Otherwise the 

coils and the internal components of the equip-

ment might undergo serious and permanent 
damage in terms of corrosion.

Warnings for the quality of water circulating in 

the coils. We recommend performing an analy-

sis of the water circulating in the coil focused 

on searching for any bacteria (detection of iron 

bacteria and micro-organisms that can produce 

H2S or chemically reduce sulphates) and the 

chemical composition of the water itself to pre-

vent corrosion and encrustations inside the 

pipes.

The water circuit must have all the components, 

such as for instance relief and drainage systems, 

shut-off valves and that the results of the analy-

sis performed suggest are necessary to ensure 

suitable water treatment. The water treatment 

system must ensure compliance with the follow-

ing chemical and physical parameters:

Total hardness in 

mmol/l

l < mmoll/l < 1.5

Chlorides [CL 

-

]

< 10 mg/litre

Sulphates [SO

4

2-

]

< 30 mg/litre

Nitrates [NO

3

-

]

= 0 mg/litre

Dissolved iron

< 0.5 mg/litre

Dissolved oxygen

4 < [O

2

] < 9 mg/litre

Carbon dioxide [CO

2

]< 30 mg/litre

Resistivity

20 Ohm∙m < Resistivity < 50 Ohm∙m

pH

6.9 < pH < 8

OPERATING ENVIRONMENT

C/F

C

VC/F

VC

C/F

C

VC/F

VC

SA

VC/F

VC

SA

VC/F

SA

C/F

VC/F

SA

C/F

SA

C/F

SA

SW

VC/F

VC

SA

SW

VC/F

VC

SA

C/F

C

SW

VC/F

C/F

VC/F

SA

SW

C/F

SA

SW

C/F

SW

SA

SW

VC/F

VC

SA

SW

VC/F

VC

SA

C/F

C

SW

VC/F

C/F

VC/F

SA

SW

C/F

SA

SW

C/F

SW

SYSTEM EXAMPLES

KEY:

SW

Water temperature probe

VC/F

Valve (Heating / Cooling)

VC

Valve (Heating) 

SA

 

Room temperature probe

H/C 

Coil 

(Heating / Cooling)

C

Coil 

(Heating)

2-PIPE SYSTEM WITH WATER PROBE

HORIZONTAL INSTALLATION 

2-PIPE SYSTEM WITHOUT WATER PROBE

4-PIPE SYSTEM WITH WATER PROBE

4-PIPE SYSTEM WITHOUT WATER PROBE

C/F

C

VC/F

VC

C/F

C

VC/F

VC

SA

VC/F

VC

SA

VC/F

SA

C/F

VC/F

SA

C/F

SA

C/F

Содержание VED 030 I

Страница 1: ...EUR for horizontal and vertical ducted installation pour installation canalis e horizontale et verticale EU EUW EUTH EUTL Technical Manual Manuel Technique 110 240 V 50 60Hz 030 040 130 140 230 240 33...

Страница 2: ...roduct without the obligation to give prior notice Thank you again AERMEC S p A index important information and maintenance 4 system examples 5 description of the unit 6 accessories 6 main components...

Страница 3: ...Gewicht die 25kg bersteigt NO transportar la m quina solos si su peso es superior a los 25Kg NON lasciare gli imballi sciolti durante il trasporto Non rovesciare DO NOT leave boxes unsecured during tr...

Страница 4: ...he filter is excessively dirty Repeat the operation more frequently if required Clean often and use a suction device to remove accumulated dust When the filter is clean reassemble it onto the fan coil...

Страница 5: ...rcuit must have all the components such as for instance relief and drainage systems shut off valves and that the results of the analy sis performed suggest are necessary to ensure suitable water treat...

Страница 6: ...tings and isolated copper pipes For main coils 24V power supply VCF2_H_24V Kit made up from motorised 2 way valves with fittings and copper pipes For heating only coils 24V power supply Control panel...

Страница 7: ...nverter device it is possible to continuously control the rotor speed and torque by simply acting on the stator currents The electric motor is buffered with elastic supports and the steel shaft is mou...

Страница 8: ...3 37 4 3 37 4 3 37 4 3 37 4 3 37 4 3 37 4 21 C 69 8 F 6 42 8 5 41 4 39 2 3 37 4 3 37 4 3 37 4 23 C 73 4 F 8 46 4 7 44 6 6 42 8 5 41 5 41 The earth leakage current of several devices placed under the...

Страница 9: ...01 2 71 2 21 3 99 3 55 2 97 4 16 3 81 3 16 Pressure drops 2 psi 4 50 3 63 2 47 2 32 1 89 1 31 4 50 3 92 3 05 Cooling Performance Total cooling capacity 3 BTU h 13 717 12 386 9 895 17 061 15 082 12 557...

Страница 10: ...200 400 600 800 1000 1200 1400 1600 1800 0 0 881 1 761 2 642 3 522 4 403 5 283 6 164 7 045 7 925 VED 030I VED 040I VED 130I VED 140I VED 230I VED 240I VED 330I VED 340I 0 10 20 30 40 50 60 70 80 90 0...

Страница 11: ...ut Pa psi VED030I 0 20 40 60 80 100 120 0 0 0029 0 0058 0 0087 0 0116 0 0145 0 0174 0 100 200 300 400 500 600 0 59 118 177 325 294 353 2 V 5 V 7 V 9 V 0 20 40 60 80 100 120 0 200 400 600 800 1000 VED1...

Страница 12: ...IN COOLING MODE IN HEATING MODE f 63 61 59 57 55 54 52 50 48 46 45 43 Average glycol water temperature Corrective factor f 63 64 61 59 57 55 54 52 50 48 46 45 43 Average glycol water temperature Corre...

Страница 13: ...34 0 29 5 32 7 31 4 27 0 21 9 20 6 16 2 2000 34 0 32 6 28 4 31 2 29 8 25 6 19 4 18 0 13 9 2500 31 5 30 1 26 0 28 3 26 8 23 0 15 7 14 1 10 8 3150 28 3 26 6 23 6 25 1 23 2 20 6 12 6 10 6 8 3 4000 24 1...

Страница 14: ...29 5 33 5 32 4 26 9 24 7 23 6 18 2 2000 34 8 33 6 28 4 31 9 30 8 25 5 22 2 21 0 15 9 2500 32 3 31 1 26 0 29 0 27 8 22 9 18 5 17 1 12 8 3150 29 0 27 6 23 6 25 8 24 2 20 5 15 2 13 6 10 3 4000 24 8 23 7...

Страница 15: ...34 5 33 4 27 9 26 7 25 6 20 2 2000 36 8 35 6 30 4 32 9 31 8 26 5 24 2 23 0 17 9 2500 34 3 33 1 28 0 30 0 28 8 23 9 20 5 19 1 14 8 3150 31 0 29 6 25 6 26 8 25 2 21 5 17 2 15 6 12 3 4000 26 8 25 7 20 4...

Страница 16: ...800 49 3 47 5 44 6 46 6 44 8 41 9 26 1 24 4 21 2 1000 46 9 46 0 39 7 43 3 42 5 36 0 25 1 24 2 17 5 1250 43 9 42 5 38 5 40 4 39 0 34 8 21 5 20 2 15 6 1600 39 3 38 0 33 5 35 7 34 4 29 9 15 9 14 6 10 2...

Страница 17: ...des installations dans des milieux tr s fr quent s ou qui exigent des stan dards d hygi ne lev s PENDANT LE FONCTIONNEMENT Laisser toujours le filtre mont sur le venti lo convecteur durant le fonction...

Страница 18: ...question de fa on pr venir l ins tauration des ph nom nes de corrosion et d incrustation de l int rieur des tuyaux Le circuit de l eau doit tre quip de tous les composants comme par exemple des syst m...

Страница 19: ...c coque isolante raccords et tubes cuivre isol s Pour les bobines principales Alimentation 24V VCF4_H_24V Kit made up from motorised 3 way valves fittings and isolated copper pipes For heating only co...

Страница 20: ...is dans les ventilo convecteurs modulants d AERMEC pr sente de tr s gros avantages par rapport aux moteurs traditionnels courant altern et aux moteurs hybrides et inverseur sans sondes effet Hall g n...

Страница 21: ...rche la temp rature moyenne de l eau ne doit pas tre inf rieure aux limites indiqu es dans le tableau ci des sous qui d pendent des conditions ther miques et hygrom triques de l air ambiant Ces limite...

Страница 22: ...50 3 63 2 47 2 32 1 89 1 31 4 50 3 92 3 05 Performance de rafra chissement Puissance frigorifique totale 3 BTU h 13 717 12 386 9 895 17 061 15 082 12 557 18 289 16 344 13 580 Puissance frigorifique se...

Страница 23: ...haque changement de la temp rature moyenne de l eau Temp rature moyenne de l eau C 41 50 59 68 122 140 158 F 105 122 138 154 251 284 316 Coefficient de multiplication 1 03 1 0 96 0 91 0 78 0 75 0 72 P...

Страница 24: ...trique utile Pa psi VED030I 0 20 40 60 80 100 120 0 0 0029 0 0058 0 0087 0 0116 0 0145 0 0174 0 100 200 300 400 500 600 0 59 118 177 325 294 353 2 V 5 V 7 V 9 V 0 20 40 60 80 100 120 0 200 400 600 800...

Страница 25: ...nne de l eau glycol e Facteur de correction Temp rature moyenne de l eau glycol e Facteur de correction Temp rature moyenne de l eau glycol e Facteur de correction Temp rature moyenne de l eau glycol...

Страница 26: ...315 47 2 45 7 41 9 45 6 44 0 40 4 38 1 36 7 32 5 400 49 4 48 0 43 8 47 3 45 9 41 8 39 3 38 0 33 4 500 47 0 45 5 41 9 44 9 43 3 39 7 37 1 35 3 32 2 630 44 5 42 8 39 7 42 6 40 9 37 8 36 3 34 1 32 3 800...

Страница 27: ...600 36 1 35 0 29 5 33 5 32 4 26 9 24 7 23 6 18 2 2000 34 8 33 6 28 4 31 9 30 8 25 5 22 2 21 0 15 9 2500 32 3 31 1 26 0 29 0 27 8 22 9 18 5 17 1 12 8 3150 29 0 27 6 23 6 25 8 24 2 20 5 15 2 13 6 10 3 4...

Страница 28: ...0 2 2000 36 8 35 6 30 4 32 9 31 8 26 5 24 2 23 0 17 9 2500 34 3 33 1 28 0 30 0 28 8 23 9 20 5 19 1 14 8 3150 31 0 29 6 25 6 26 8 25 2 21 5 17 2 15 6 12 3 4000 26 8 25 7 20 4 22 4 21 3 15 8 12 9 10 4 9...

Страница 29: ...33 5 35 7 34 4 29 9 15 9 14 6 10 2 2000 38 0 36 6 32 4 34 2 32 8 28 5 13 4 12 0 7 9 2500 35 5 34 1 30 0 31 2 29 8 25 9 9 7 8 1 4 8 3150 32 3 30 6 27 6 28 1 26 2 23 5 6 6 4 6 2 3 4000 28 1 26 7 22 4 23...

Страница 30: ...ED340I A inch 8 54 8 54 8 54 8 54 8 54 8 54 8 54 8 54 B inch 21 65 21 65 30 75 30 75 39 41 39 41 44 17 44 17 C inch 22 05 22 05 22 05 22 05 22 05 22 05 22 05 22 05 D inch 25 55 25 55 34 65 34 65 43 31...

Страница 31: ...8 0 5 156 2 0 7 7 2 0 7 1 4 3 3 98 EU EUTH EUTL D B C A Vers EU EUTH EUTL VED030I VED040I VED130I VED140I VED230I VED240I VED330I VED340I A inch 8 54 8 54 8 54 8 54 8 54 8 54 8 54 8 54 B inch 21 65 21...

Страница 32: ...l y u p d a t e d P l e a s e r e f e r t o t h e o n e s s u p p l i e d w i t h t h e u n i t Nos sch mas lectriques tant constamment mis jour il faut absolument se r f rer ceux fournis bord de nos...

Страница 33: ...ema beziehen El cableado de las m quinas es sometido a actualizaciones constantes Por favor para cada unidad hagan referencia a los esquemas suministrados con la misma TARGHETTA AUTOADESIVA IN POLIEST...

Страница 34: ...A se r serve le droit de modifier tous moments les donn es consid r es n cessaires l amelioration du produit Technical data shown in this booklet are not binding AermecS p A shallhavetherighttointrod...

Отзывы: