12.2 Alarm reset 
 

When an alarm/error condition persists on the unit, it is signalled on the 
main screen of the display with "

Alarm

" and the lighting of the 

red led 

flashing 

or 

fixed

 
To know the cause that generated the alarm, simply press and hold the 
F3 key (shortcut) of the FUNCTION key;  

the screen shows a first part with the Bios Alarms, User Alarms and 
Probe Errors and a second part proposes the Alarms reset option, an 

alarm log and the cancel option of the alarms log (option that can be 
performed by entering the password). 

 

 

 
 

The High and Low temperature alarms are reset:

- Manually if resettable
- When the system is turned on or off;

- When exiting the configuration mode 

;

- Press ENTER/PUSH from the MENU to select the “Bios Alarms”; the 
display may show “EMPTY” meaning that the alarm signalled 

is not 

in 

the Bios or it may show the wording of the type of alarm detected. 
Press the ESC key and try to see, moving with the UP - DOWN keys, if 

an alarm in the User alarms is detected. The same procedure can be 
used to check the Probe Errors.

- Having established what type of error has been detected, with the UP 
- DOWN keys, select Reset Alarms and press ENTER/PUSH of the 

MENU: "OK" is displayed for a fraction of a second and, resetting the 
alarm, the alarms screen appears again.

Note that the option "Cancel Log" is active after entering the

password

By pressing the ESC key of the MENU, the system returns to the main 

screen; the wording “

Alarms” 

changes into 

“No alarm”

and the red 

LED switches off 

.

Hh:mm           NRGXTPRO            01/02 

Hot                                               ! Alarms 
Room Temp.  

 

  19.8  °C 

Set Point   

 

      

 

ALARMS   

 

         01/02 

Bios Alarms 

                                    

User Alarms 
Probe errors

 

 

 

     

 

 

EMPTY

 

 

 

 

ALARMS   

 

         02/02 

Alarms Reset 

 Log 
Cancel Log

 

 

 

     

Hh:mm           NRGXTPRO            01/02 

Hot  

                                    No Alarm 

Room Temp.  

 

  19.8  °C 

Set Point   

 

      

 

Содержание RTE240

Страница 1: ...RTE units User manual 0412 6180480 Rev 00 RTE 240 400...

Страница 2: ...User manual RTE Page 2 of 25 0412 6180480 Rev 00...

Страница 3: ...page 4 Responsibilities and residual risks page 4 WEEE Directive page 4 DIAGRAM of the parameter masks page 5 User interface page 7 Switching on and off page 9 Modifying the SET POINT page 11 Selecti...

Страница 4: ...RESPONSABILITIES AND RESIDUAL RISKS AERMEC SpA are not liable for any damages arising from installation use other than that prescribed and in particular that does not comply with safety requirements...

Страница 5: ...User manual RTE Page 5 of 25 0412 6180480 Rev 00 6 DIAGRAM OF THE PARAMETERS MASKS This menu can be accessed without PASSWORD...

Страница 6: ...User manual RTE Page 6 of 25 0412 6180480 Rev 00 This menu can only be accessed with PASSWORD...

Страница 7: ...User manual RTE Page 7 of 25 0412 6180480 Rev 00...

Страница 8: ...ch in the ON position even when off or in stand by it will be off if the device is not powered main switch set to OFF Yellow Led 2 second from the top Indicates that there is communication between the...

Страница 9: ...n the wiring diagram of the unit The indications for fixing the remote keyboard to a suitable support are included in the packaging of the accessory itself The accessory normally comes packed and posi...

Страница 10: ...n switched off In the event of power failure during the shut down procedure of the machine when the power returns the machine restarts Off standby If the unit has already been activated with the Push...

Страница 11: ...y 4 lines at a time The second screen or the subsequent screens can be displayed by pressing the arrow keys at the bottom of the Menu keys group NB The following screens can be displayed also by press...

Страница 12: ...ER PUSH to modify it the value flashes 4 UP arrow or DOWN arrow to modify it 5 ENTER PUSH to confirm Left arrow ESC to end the editing of the value selected 6 Left arrow ESC to return to the initial s...

Страница 13: ...be used during warm weather to produce cool cold air HOT will be used during colder weather to produce hot air Depending on the temperatures set in the SET POINT AUTO automatically manages the operati...

Страница 14: ...to set or not the application TIMER ENTER right key to make the YES NO flash UP DOWN key to perform the desired variation confirm with ENTER and exit a level with ESC ESC The TIMER TYPE can be selecte...

Страница 15: ...th the UP DOWN keys till you find SETTINGS then press ENTER all the days of the week that can be selected via the UP DOWN keys appear select the desired day by pressing ENTER e g Monday SLOT1 appears...

Страница 16: ...ing defined the parameters of the previously listed MANUAL SETPOINTS press the ESC button once to return to the previous menu DOWN key ENTER to select the OPTIONS that can be THE OPTIONS MENU provides...

Страница 17: ...ress ESC to exit by one level All of these adjustments must be made for each individual day of the week Timer type WEEKLY for this type of selection the software manages each day of the week in the sa...

Страница 18: ...resolution of all alarms the presence of which is shown by the red LED with fixed light please contact the AERMEC service department Cumulative alarm relay The presence of active alarms with manual re...

Страница 19: ...larms the display may show EMPTY meaning that the alarm signalled is not in the Bios or it may show the wording of the type of alarm detected Press the ESC key and try to see moving with the UP DOWN k...

Страница 20: ...THERMAL SWITCH FILTERS BLOCKED FILTERS DIRTY AIR FLOW HEATERS THERMAL SWITCH THERMAL SWITCH HEAT 1 THERMAL SWITCH HEAT 2 THERMAL SWITCH HEAT 3 THERMAL SWITCH HEAT 4 DUAL STAGE GEN THERMAL SWITCH SMOK...

Страница 21: ...RMEC service Dept CRC EEPROM USER ERROR The default of the parameters are automatically reset Evaluate to restore parameters or replacement by the AERMEC service Dept REAL TIME CLOCK NEED TO BE SET Se...

Страница 22: ...eeded Reset alarm and check filters Manual FILTERS DIRTY Display only Filters dirty Clean replace Manual AIR FLOW System block Contact the Service centre Manual HEATERS THERMAL SWITCH Operation block...

Страница 23: ...ace component Automatic HUMIDITY LIMIT Disables humidifier delivery limit Delivery humidity probe error Check wiring or replace component Automatic EXTERNAL HUMIDITY Disables enthalpy economizer freec...

Страница 24: ...User manual RTE Page 24 of 25 0412 6180480 Rev 00...

Страница 25: ...96 Tel 39 0442 633111 Telefax 39 0429 93730 39 0442 93566 www aermec com The technical data in this document are not binding AERMEC S p A reserves the right to make changes at any time deemed necessar...

Отзывы: