Manual selection, installation and maintenance
12
Roof-top units -
RTE series
-
Cooling only F (standard) R 410A
Referring to:
Ambient air 27 °C/ 50% r.h.
Outside air 35 °C
* Energy index refers to the cooling circuit
025F
030F
040F
050F
080F
090F
100F
150F
200F
Cooling capacity
kW
10,5
12,4
15,7
18,5
23,6
27,9
37,1
45,2
52,3
Sensible nominal cooling capacity
kW
6,7
8,2
10,1
11,9
15,5
18,1
24,1
30,7
34,0
Cooling imput power
kW
2,4
2,8
3,3
3,9
5,3
6,0
7,9
10,6
12,1
Cooling absorbed power
A
4,7
5,0
5,8
7,2
10,4
11,6
15,3
19,1
24,5
E.E.R.
*
F
3,5
3,5
3,6
3,5
3,4
3,5
3,8
3,4
3,4
Condensing system section
Compressor
Compressor type
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Number / circuit
n.ro
1/1
1/1
1/1
1/1
1/1
1/1
1/1
1/1
1/1
Capacity control steps
%
0-100
0-100
0-100
0-100
0-100
0-100
0-100
0-100
0-100
Starting current
A
40
46
43
49
101
99
96
96
198
Refrigerant charge R 410A
Kg
To call AERMEC S.p.A. technical office
Fan
Number x Installed power
n.ro x kW 1 x 0,15
1 x 0,15
1 x 0,25
1 x 0,25
1 x 0,52
1 x 0,52
4 x 0,15
4 x 0,15
4 x 0,15
Air flow
m
3
/h
3500
3500
4800
6200
8000
8000
14000 14000 14000
Evaporator
Number
n°
1
1
1
1
1
1
1
1
1
Air handling section
Fan
Nominal air flow
m
3
/h
1500
1900
2400
2900
4000
4500
6000
8000
9000
Number
n°
1
1
1
1
2
2
2
2
2
Total installed power
kW
0,47
0,55
0,80
1,00
0,98
1,17
1,31
1,90
2,47
Prevalence guaranteed
Pa
200
Air filters
Thickness
mm
50
50
50
50
50
50
50
50
50
Efficiency
G4
G4
G4
G4
G4
G4
G4
G4
G4
Operating limits
Maximun external temperature
°C
46
46
46
46
46
46
46
46
46
Maximun internal temperature
°C
30
30
30
30
30
30
30
30
30
Minumum internal temperatur
°C
18
18
18
18
18
18
18
18
18
Minimum airflow for the handling section
m
3
/h
1375
1615
2120
2500
3285
3610
5045
6672
7595
Sizes base version
Height
mm
1032
1038
1038
1038
1172
1188
1500
1500
1500
Detph
mm
1175
1175
1175
1175
1240
1800
1510
1510
1510
Length
mm
1154
1155
1155
1155
1804
1240
2710
2710
2710
Net weight F vers
Kg
235
250
270
285
435
450
650
675
735
Hot water heating coil (accessory) BRT2
Number of rows
n°
2
2
2
2
2
2
2
2
2
Capacity
kW
16,3
19,2
22,5
25,5
36,1
39,0
57,0
68,9
74,4
Water flow rate
l/h
1440
1690
1980
2250
3180
3440
5020
6070
6550
Pressure drop
kPa
16
24
32
40
44
52
32
44
52
Hot water heating coil (accessory) BRT3
Number of rows
n°
3
3
3
3
3
3
3
3
3
Capacity
kW
22,5
27,0
32,2
37,1
52,1
56,8
81,8
100,4
109,3
Water flow rate
l/h
1980
2380
2840
3270
4590
5000
7150
8850
9630
Pressure drop
kPa
24
36
48
60
57
66
39
57
66
Electrical power
Type
V/ph/Hz
400/3 + N/50
1
1
1
1
1
2
3
3
3
Referring to:
Ambient air 20 °C
Outside air 7 °C bs / 70% U.R.
Referring to:
Ambient air 20 °C
Water 80/70 °C
RTE