![AERMEC NXW 0500-1650 Скачать руководство пользователя страница 20](http://html.mh-extra.com/html/aermec/nxw-0500-1650/nxw-0500-1650_installation-manual_2862069020.webp)
20
21.02 – 4438830_05
WEIGHT DISTRIBUTION AND CENTRES OF GRAVITY
C
D
A
B
Yg
Xg
Model
Hydronic kit Empty weight (lbs)
Centre of mass
A
B
C
D
Xg (in)
Yg (in)
%
%
%
%
WITHOUT HYDRONIC KIT
NXW 0500 L
°
1,610
15.4
36.6
25.5%
24.3%
25.7%
24.5%
NXW 0550 L
°
1,744
15.7
35.0
26.2%
25.9%
24.1%
23.8%
NXW 0600 L
°
1,746
15.7
35.0
26.2%
25.9%
24.1%
23.8%
NXW 0650 L
°
1,935
15.9
36.5
24.7%
25.2%
24.8%
25.3%
NXW 0700 L
°
1,955
16.0
36.5
24.6%
25.3%
24.7%
25.4%
NXW 0750 L
°
2,270
16.0
46.7
22.1%
22.8%
27.1%
28.0%
NXW 0800 L
°
2,364
15.9
49.9
23.6%
24.0%
26.0%
26.4%
NXW 0900 L
°
2,789
16.2
47.1
24.5%
26.1%
24.0%
25.4%
NXW 1000 L
°
3,458
16.5
51.2
22.1%
24.2%
25.6%
28.1%
NXW 1250 L
°
3,696
16.4
51.9
21.9%
23.7%
26.1%
28.3%
NXW 1400 L
°
4,026
16.4
53.0
21.3%
23.1%
26.7%
28.9%
NXW 1500 L
°
4,165
16.3
53.5
21.2%
22.7%
27.1%
29.0%
NXW 1650 L
°
4,252
16.4
53.0
21.4%
23.0%
26.7%
28.9%
Weight distribution and centres of gravity when empty
WATER COOLED HEAT PUMP REVERSIBLE WATER SIDE
Operation weight: contact the factory
Содержание NXW 0500-1650