14
0280
0300
0330
0350
0500
0550
0600
0650
0700
HIGH STATIC PRESSURE CIRCULATION PUMP
Input power
KW
°
-
-
-
-
1,85
1,85
3,0
3,0
3,0
L
1,5
1,5
1,5
1,5
Absorbed current
A
°
-
-
-
-
5,0
5,0
5,7
5,7
5,7
L
3,6
3,6
3,6
3,6
Useful static pressures
KPa
°
-
-
-
-
161
150
184
178
134
L
143
144
135
129
179
168
210
198
162
SOUND DATA
Sound power (1)
dBA
°
-
-
-
-
82
82
82
83
83
L
73
73
74
75
77
77
77
78
78
Sound Pressure (2)
dBA
°
-
-
-
-
50
50
50
51
51
L
41
41
42
43
45
45
45
46
46
DIMENSIONS
Height
mm
°
-
-
-
-
1875
1875
1875
1875
1875
L
1606
1606
1606
1606
Width
mm
°
-
-
-
-
1100
1100
1100
1100
1100
L
1100
1100
1100
1100
Depth
mm
°
-
-
-
-
2950
2950
2950
2950
2950
L
2450
2450
2450
2450
2950
2950
2950
2950
3950
Empty weight
Kg
°
-
-
-
-
868
872
968
983
1091
L
675
684
688
704
REFERENCE NOMINAL CONDITIONS
IN COOLING MODE
- Inlet water temperature
12 °C
- Outlet water temperature
7 °C
- External air temperature
35 °C
-
∆
t
5°C
(1)
SOUND POWER
Aermec determines sound power values in agreement with
the 9614-2 Standard, in compliance with that requested by
Eurovent certification.
(2)
SOUND PRESSURE
Sound pressure measured in free field conditions with
reflective surface (directivity factor Q=2) at 10mt distance
from external surface of unit, in compliance with ISO 3744
regulations.
NRL_Tecnico (standard-silenziata3)_01_EN.indd 014
22/06/2009 11.47.20