33
NRL 028-075 60Hz
EN
18. PART LOAD
LEVELS OF POWER
COOLING CAPACITY %
1%
2%
3%
4%
028
55
100
-
-
030
55
100
-
-
033
55
100
-
-
035
55
100
-
-
050
40
75
100
-
055
36
68
100
-
060
25
50
75
100
065
28
50
78
100
070
25
50
75
100
075
27
53
77
100
POWER INPUT %
1%
2%
3%
4%
028
45
100
-
-
030
45
100
-
-
033
45
100
-
-
035
45
100
-
-
050
30
65
100
-
055
26
58
100
-
060
20
45
70
100
065
23
45
73
100
070
20
45
70
100
075
23
47
73
100
HEATING CAPACITY %
1%
2%
3%
4%
028
50
100
-
-
030
50
100
-
-
033
50
100
-
-
035
50
100
-
-
050
35
70
100
-
055
31
63
100
-
060
23
48
73
100
065
25
47
75
100
070
23
48
73
100
075
25
47
75
100
POWER INPUT %
1%
2%
3%
4%
028
45
100
-
-
030
45
100
-
-
033
45
100
-
-
035
45
100
-
-
050
30
65
100
-
055
26
58
100
-
060
20
45
70
100
065
23
45
73
100
070
20
45
70
100
075
23
47
73
100
HEATING (AHRI CONDITIONS)
Inlet water temperature
40°C / 104°F
Outlet water temperature
45°C / 113°F
External air temperature
7°C_44.6°F B.S. / 6°C_42.8°F B.U.
COOLING (AHRI CONDITIONS)
Outlet water temperature
6,7°C / 44,6°F
Flow rate
0,043l/s per kW
External temperature
35°C / 95°F