-  Install the unit at a distance enough from the exhaust wells, to ensure 

that the possible loss of gas may reach and pollute the aquifer

-  Keep all lubricants in properly marked containers do not keep 

flammable liquids near the plant 

-  Do not remove the protections from mobile elements while the unit 

is running 

-  Do not use cables with inadequate section or flying connections, not 

even for limited periods or emergencies 

-  Check the unit is properly earthed before starting it 

-   Before opening the electrical panel, disconnect the unit from the 

mains by means of the external isolator 

-  In case of units with shunt capacitors, wait 3 minutes from when 

power supply was disconnected from the unit before accessing inside 

the electrical panel 

-  If the unit is equipped with integrated inverter compressors, 

disconnect the power supply and wait at least 15 minutes before 

accessing for maintenance: the internal components remain live for 

this time, generating the risk of electrocution 

-  The safety devices must be maintained efficient and periodically 

checked as prescribed by current regulations 

-  In case a piece is disassembled, make sure it is correctly reassembled 

before restarting the unit 

-  Even with the unit off, prevent the fluid in contact with the 

heat exchangers exceed the temperature limits indicated in the 

documentation and freeze.

-  Do not send the heat exchangers fluids other than water or its 

mixtures with ethylene glycol/propylene in a maximum concentration 

of 30% 

-  The machine must only be employed for the use for which it was 

made; any other use can be dangerous and void the warranty

P

REVENTIONS

-  Make sure that the protections of mobile elements are correctly in 

place before restarting the unit 

-  Fans, motors and belt drives may be in motion: always wait for them 

to stop and take appropriate precautions to prevent their activation 

before accessing them 

-  The machine and the pipes have very hot and very cold surfaces that 

lead to risk of burns

-  Before opening a machine panel, ascertain whether it is or not firmly 

connected to it by hinges 

-  Louvers of the heat exchangers, edges of the components and metal 

panels can generate cuts

 -  The installation must ensure that the temperature of the fluid 

entering the unit is maintained stable and within the provided limits; 

therefore, pay attention to the adjustment of any external thermal 

exchange and control devices (drycooler, evaporating towers, 

area valves, ...), to the adequate dimensioning of the mass of fluid 

circulating in the plant (in particular when plant areas are excluded) 

and to install systems for the recirculation of the necessary fluid flow 

rate so as to maintain the machine temperatures within the allowed 

limits (e.g. during the start-up phase). 

-  The material used for the machine protective packaging must always 

be kept out of the reach of children as it is a source of danger 

-  In units with compressors in parallel, do not disable the individual 

compressors for long periods.

-  This is an appliance not accessible to the general public.

Содержание NRK 0150 A

Страница 1: ...f r o m o r i g i n a l I n s t a l l a t i o n m a n u a l EN 60Hz REVERSIBLE AIR WATER HEAT PUMP C o o l i n g c a p a c i t y 8 8 3 9 7 t o n H e a t i n g c a p a c i t y 1 1 6 8 6 6 5 9 3 2 3 5 B T U h NRK 0150 0700 2 1 0 5 5 1 6 7 5 5 7 _ 0 2 ...

Страница 2: ......

Страница 3: ...nt to present the product and help you select the unit that best meets the needs of your system However please note that for a more accurate selection you can also use the Magellano selection program available on our website Aermec Aermec always attentive to the continuous changes in the market and its regulations reserves the right to make all the changes deemed necessary for improving the produc...

Страница 4: ...lectronic Equipment WEEE please return the device using appropriate collection systems or contact the retailer where the product was purchased Please contact your local authority for further details Illegal dumping of the product by the user entails the application of administrative sanctions provided by law All specifications are subject to change without prior notice Although every effort has be...

Страница 5: ...unts 11 Position of hydraulic connections 15 Weight distribution 17 Minimum technical spaces 20 Hydraulic connections 21 Main hydraulic circuits 22 Electrical connections 28 Electric power connection to the electrical mains 29 Commissioning warnings 30 Maintenance 31 Maintenance list of the recommended periodic interventions 34 ...

Страница 6: ...make any necessary repairs The installation must comply with the requirements of EN378 3 and the local current regulations In particular indoor installation must ensure adequate ventilation and provide refrigerant detectors when necessary The machine must not be installed in environments with risk of explosion but in a suitable place In particular if intended for indoor use it cannot be installed ...

Страница 7: ...r its mixtures with ethylene glycol propylene in a maximum concentration of 30 The machine must only be employed for the use for which it was made any other use can be dangerous and void the warranty PREVENTIONS Make sure that the protections of mobile elements are correctly in place before restarting the unit Fans motors and belt drives may be in motion always wait for them to stop and take appro...

Страница 8: ...loaded with refrigerant make sure there have been no leaks Check that the equipment supplied corresponds to the order and delivery note Product identification The Aermec products can be identified by the packaging label bearing the identification data of the product and by the technical plate bearing the performance and technical data of your unit If the product is damaged send a registered letter...

Страница 9: ...ts for handling ATTENTION The unit comes fixed on a pallet Use forklifts for handling ATTENTION Lifting rods NOT supplied ATTENTION Diameter of holes Ø 40 HANDLING 0150 0700 If accessory CRATE is included LIFTING 0300 0700 Accessory Size Height Width Length CRATE_ANL 0150 in 60 6 37 9 74 7 CRATE02 0300 0330 0350 0550 in 82 7 49 1 135 8 CRATE03 0600 0650 0700 in 82 7 49 1 177 1 ...

Страница 10: ...sistance Check that the contact surfaces of the anti vibration supports are levelled to the base If necessary use spacers or level the base but in any case make sure that the anti vibration supports rest flat on the base surface It is essential that the units are installed leaving sufficient space around them to allow easy access to the components for maintenance and repair purposes Only for air coo...

Страница 11: ...ENSIONS LIFTING POINTS ANTIVIBRANT POSITION MOUNTS NRK 0150 A 68 8 in 29 7 in 29 6 in 5 5 in 57 1 in 4 0 in 4 0 in 3 0 in 62 9 in 69 1 in 3 0 in 27 9 in Size 0150 Dimensions package Height in 62 3 Width in 34 3 Depth in 72 9 ...

Страница 12: ...12 21 05 5167557_02 NRK 0300 A 63 3 in 43 3 in 7 9 in 110 3 in 7 9 in 23 6 in 25 4 in 126 1 in Size 0300 Dimensions package Height in 70 1 Width in 45 7 Depth in 128 4 ...

Страница 13: ... in 41 8 in 43 3 in 131 5 in 23 2 in 28 7 in 0 8 in 0 8 in 7 9 in 51 5 in 51 5 in 20 6 in NRK 0330 0350 0550 A Size 0330 0350 0550 Dimensions package Height in 79 9 79 9 79 9 Width in 46 1 46 1 46 1 Depth in 133 8 133 8 133 8 ...

Страница 14: ...73 9 in 43 3 in 170 6 in 43 3 in 0 8 in 0 8 in 8 1 in 85 0 in 56 7 in 20 7 in 41 8 in NRK 0600 0650 0700 A Size 0600 0650 0700 Dimensions package Height in 79 4 79 4 79 4 Width in 46 1 46 1 46 1 Depth in 172 8 172 8 172 8 ...

Страница 15: ... AS STANDARD FOR SIZES 0300 0330 0350 0550 0600 0650 0700 Grooved joints EU Grooved joint USA Grooved nipple USA Reduction adapter EU USA IN Water 1 1 4 OUT Water 1 1 4 29 6 in 29 6 in 5 5 in 4 0 in 20 4 in 43 3 in 9 7 in 13 6 in 22 8 in 43 3 in 9 7 in 13 6 in 16 9 in 43 3 in 9 7 in 13 6 in 27 8 in 3 9 in 0 6 in 0 6 in 0 3 in 0 3 in 0 1 in 0 1 in ...

Страница 16: ...RK 0330 0350 0550 0600 0650 0700 A 00 NRK 0330 0350 0550 0600 0650 0700 A 01 04 NRK 0330 0350 0550 0600 0650 0700 A P1 P4 43 3 in 9 7 in 13 6 in 22 9 in 43 3 in 9 7 in 13 6 in 28 0 in 43 3 in 21 7 in 9 7 in 13 6 in 16 8 in ...

Страница 17: ...21 05 5167557_02 17 WEIGHT DISTRIBUTION A B C D A B C D A B C D A B C D E F Xg Yg Xg Yg Xg Yg Xg Yg NRK 0150 NRK 0300 NRK 0330 0550 NRK 0600 0700 top view top view top view top view ...

Страница 18: ... 59 1 27 28 22 23 02 04 2 387 21 9 62 9 26 26 24 24 01 03 2 339 21 9 61 9 26 27 23 24 0550 00 1 955 21 9 57 1 28 29 21 22 P2 P4 2 118 21 9 60 1 27 27 23 23 P1 P3 2 070 21 9 59 2 27 28 22 23 02 04 2 405 21 9 62 9 26 26 24 24 01 03 2 356 21 9 61 9 26 27 23 24 0600 00 2 544 21 7 66 6 12 12 30 30 8 8 P2 P4 2 711 21 7 69 0 11 11 31 31 8 8 P1 P3 2 661 21 7 68 4 11 11 31 31 8 8 02 04 2 998 21 7 70 8 9 9 ...

Страница 19: ...23 VT11 02 04 3 532 21 8 68 9 24 24 26 26 VT11 01 03 3 484 21 8 68 3 24 24 26 26 VT11 0550 00 1 976 21 9 57 1 28 29 21 22 VT11 P2 P4 2 161 21 9 60 4 27 27 23 23 VT11 P1 P3 2 112 21 9 59 5 27 28 22 23 VT11 02 04 3 550 21 8 68 9 24 24 26 26 VT11 01 03 3 501 21 8 68 3 24 24 26 26 VT11 0600 00 2 572 21 7 66 5 12 12 31 31 8 8 VT22 P2 P4 2 761 21 7 69 2 10 10 31 32 8 8 VT22 P1 P3 2 711 21 7 68 7 11 11 3...

Страница 20: ... C2 Size 0150 0300 0330 0350 0550 0600 0650 0700 Minimumtechnicalspaces A1 in 118 2 118 2 118 2 118 2 118 2 118 2 118 2 118 2 B1 in 31 5 31 5 31 5 31 5 31 5 31 5 31 5 31 5 B2 in 43 3 43 3 43 3 43 3 43 3 43 3 43 3 43 3 C1 in 31 5 31 5 31 5 31 5 31 5 31 5 31 5 31 5 C2 in 31 5 31 5 31 5 31 5 31 5 31 5 31 5 31 5 MINIMUM TECHNICAL SPACES ...

Страница 21: ...tion of the pump High concentration of glycol could stuck the pump Do not use the pump to mix water and glycol The units may be available with or without integrated hydronic kit in any case ATTENTION The choice and installation of components external to the unit is up to the installer who must operate according to the rules of good technical design and in compliance with the regulations in force i...

Страница 22: ...ne Ammonium ions NH None Silica SiO 30 ppm WATER CHARACTERISTICS NRK 0150 00 Components as standard 1 Plate heat exchanger 2 Water temperature sensors IN OUT 3 Pressure relief valve 4 Water filter 5 Air drain valve 6 Flow switch Components not provided and responsibility of the installer 7 Anti vibration joints 8 Pump 9 Air drain valve 10 Pressure gauge 11 Expansion vessel 12 Storage tank 13 Antif...

Страница 23: ...NH None Silica SiO 30 ppm WATER CHARACTERISTICS NRK 0150 P1 P3 Components as standard 1 Plate heat exchanger 2 Water temperature sensors IN OUT 3 Water filter 4 Pump 5 Air drain valve 6 Expansion vessel 7 Pressure relief valve 8 Flow switch Components not provided and responsibility of the installer 9 Anti vibration joints 10 Flow shut off valves 11 Air drain valve 12 Pressure gauge 13 Storage tan...

Страница 24: ...ns NH None Silica SiO 30 ppm WATER CHARACTERISTICS NRK 0150 01 03 Components as standard 1 Plate heat exchanger 2 Water temperature sensors IN OUT 3 Water filter 4 Pump 5 Pressure relief valve 6 Air drain valve 7 Expansion vessel 8 Storage tank 9 Antifreeze electric heater 10 Drain valve 11 Flow switch Components not provided and responsibility of the installer 12 Anti vibration joints 13 Flow shu...

Страница 25: ...NH None Silica SiO 30 ppm WATER CHARACTERISTICS NRK 0300 0700 00 Components as standard 1 Plate heat exchanger 2 Water temperature sensors IN OUT 3 Flow switch 4 Air drain valve 5 Water filter 6 Drain valve Components not provided and responsibility of the installer 7 Anti vibration joints 8 Drain valve 9 Pump 10 Pressure gauge 11 Flow shut off valves 12 Expansion vessel 13 Air drain valve 14 Safe...

Страница 26: ...0300 0700 P1 P2 P3 P4 Components as standard 1 Plate heat exchanger 2 Water temperature sensors IN OUT 3 Flow switch 4 Expansion vessel 5 Air drain valve 6 Water filter 7 Pump P1 P3 Single pump P2 P4 Pump stand by pump 8 Check valve 9 Drain valve Components not provided and responsibility of the installer 10 Anti vibration joints 11 Drain valve 12 Pressure gauge 13 Flow shut off valves 14 Expansio...

Страница 27: ...0300 0700 01 02 03 04 Components as standard 1 Plate heat exchanger 2 Water temperature sensors IN OUT 3 Flow switch 4 Air drain valve 5 Water filter 6 Pump 01 03 Storage tank and pump 02 04 Storage tank with pump stand by pump 7 One way valve 02 04 8 Drain valve 9 Flow shut off valves 10 Expansion vessel 11 Safety valve 12 Storage tank 13 Antifreeze electric heater Components not provided and res...

Страница 28: ... related to these operations The characteristics of the electrical lines and of the related components must be determined by staff qualified to design electrical systems in compliance with the international and national regulations of the place of installation of the unit and in compliance with the regulations in force at the moment of installation For the installation requirements refer only to t...

Страница 29: ...vely to the wiring diagram supplied with the unit Remove any protections from the cable fixing points For the functional connection of the unit take the power supply cable to the electric control board inside the unit and connect it to clamps L1 L2 L3 N if present and PE respecting the polarities L1 L2 L3 and N as phases and PE as grounding Ensure that all protections removed for the electric conn...

Страница 30: ...ator pressure drop tables present in this manual Check the correct functioning of the flow meters if installed Closing the cut off valve at the output of the heat exchanger the unit control panel must show the block Finally re open the valve and rearm the block COMMISSIONING Once all the aforementioned checks have been carried out the unit can be commissioned Close the door of the electrical panel ...

Страница 31: ...ns to prevent their activation before accessing them Isolate the unit from the mains by means of the external isolator provided for the insertion of padlocks up to 3 for blocking in open position Place a sign reading Do not turn on maintenance in progress on the open isolator Equip yourself with the appropriate personal protective equipment helmet insulated gloves protective goggles accident preve...

Страница 32: ...st be replaced after draining the refrigerant gas contained in the circuit During venting protect yourself against any leakage of fluids at dan gerous temperatures and or pressures Always use appropriate equipment extractor antistatic bracelet etc when replacing electronic boards If replacing a motor compressor evaporator condensing coil or any other heavy element make sure that the lifting device...

Страница 33: ...tor to near the machine cooling circuit Access the machines and acquire the measurements keeping AWAY from the under pressure parts of the cooling circuit As soon as the measurements are taken turn off the machine remove the instruments and close the cooling circuit compartment The thermostatic valve must be calibrated with the machine off The high low pressure switch where present must be tested wi...

Страница 34: ...ts paying particular attention to under pres sure containers In this case replace them of intervene with specific products General cleaning of the unit Bleed the hydraulic circuit and the heat exchangers the simultaneous presence of air and water reduces yield and can benefit the arising of rust INTERVENTIONSTO COOLING CIRCUIT Functioning at full load Overheating temperature measurement Subcooling...

Страница 35: ...roper functioning of the thermostatic valve Check the charge of refrigerant gas 1 Check the proper functioning of the solenoid valves MAINTENANCE LIST OF THE RECOMMENDED PERIODIC INTERVENTIONS DECOMMISSIONING AND DISPOSAL OF THE MACHINE COMPONENTS ATTENTION The unit contains greenhouse effect fluoride gases covered by the Kyoto Protocol The law prohibits its dispersion in the environment and requi...

Страница 36: ...4 0 B e v i l a c q u a V R I t a l y P h o n e 3 9 0 4 4 2 6 3 3 1 1 1 F a x 3 9 0 4 4 2 9 3 5 7 7 s a l e s a e r m e c c o m w w w a e r m e c c o m 2 1 0 4 5 1 6 7 5 5 7 _ 0 2 DOWNLOAD THE LATEST VERSION http www aermec com qrcode asp q 15782 ...

Отзывы: