17
6.2 TECHNICAL DATA - STANDARD VERSION (H) 3N 400V ~ 50Hz
U.M.
0502
0802
0902
FLOOR SYSTEM HEATING MODE (1)
Heating capacity
kW
13.77
17.22
20.96
Total input power
kW
3.72
4.55
5.48
COP kW/kW
3.70
3.78
3.82
Water flow rate
l/h
2360
2960
3610
Pressure drop
kPa
20
30
36
Input current
A
8.1
10.0
11.7
FAN COIL OPERATION (2)
Heating capacity
kW
13.05
16.41
20.0
Total input power
kW
4.33
5.28
6.48
COP kW/kW
3.01
3.10
3.09
Water flow rate
l/h
2240
2820
3440
Pressure drop
kPa
18
28
33
Total input power
A
8.8
10.8
12.9
RADIATOR OPERATION AT LOW TEMPERATURES (3)
Heating capacity
kW
12,36
15.42
18.85
Total input power
kW
5.06
6.28
7.57
COP
kW/kW
2.44
2.46
2.49
Water flow rate
l/h
2360
2960
3610
Pressure drop
kPa
20
30
36
Total input power
A
10.30
12.95
15.06
COOLING MODE (3)
Cooling capacity:
kW
11.90
14.40
17.80
Total input power
kW
4.40
5.30
6.60
EER kW/kW
2.70
2.72
2.70
Water flow rate
l/h
2050
2480
3060
Pressure drop
kPa
15
22
26
Total input power
A
9.4
11.5
14.0
ELECTRICAL DATA
Total starting current
A
37
52
58
Compressor starting current
1
A
26
32
46
Compressor starting current
2
A
32
46
51
Compressor maximum input power 1
A
5
6
9
Compressor maximum input power 2
A
7
9
11
Maximum total input power
A
13.7
16.7
21.7
COMPRESSORS
Types
-----
scroll
scroll
scroll
Circuit compressors
no.
2 / 1
2 / 1
2 / 1
Capacity step control
%
40-60-100
40-60-100
50-100
FANS
Types
-----
axial
axial
axial
Quantity
no.
2
2
2
Air flow rate
m3/h
6550
6450
6450
CONDENSER
Types
-----
plates
plates
plates
Quantity
no.
1
1
1
HYDRAULIC CONNECTIONS
IN/OUT connections
Ø F
1” 1/4
1” 1/4
1” 1/4
SOUND DATA
Sound pressure in heat mode
dB(A)
39.5
40.0
40.0
Sound power in heat mode
dB(A)
71.5
72.0
72.0
Sound pressure in cooling mode
dB(A)
41.0
39.0
35.5
Sound power in cooling mode
dB(A)
73.0
71.0
67.5
DIMENSIONS
Height
mm
1580
1580
1580
Width
mm
1277
1277
1277
Depth
mm
555
555
555
H weight
kg
223
232
247
Sound power:
Aermec determines the value of the sound
power on the basis of measurements taken
in accordance with the ISO/DS 9614-2
standard in compliance with what is requi-
red by the Eurovent certification.
Sound pressure:
Sound pressure in unrestricted range on
reflecting plane (directionality fact. Q=2), at
10 m distance from the outer surface of the
unit. Complying with the standard ISO3744.
N.B.
Data stated according to: EN 14511:2004
Heating (1)
FLOOR SYSTEM
processed water temperature 35°C;
external air temperature
7°C D.B./6°C W.B.;
D
t =
5°C.
Heating (2)
FAN COILS
processed water temperature 45°C;
external air temperature
7°C D.B./6°C W.B.;
D
t =
5°C.
Heating (3)
RADIATORS AT LOW TEMPERATURES
processed water temperature 55°C;
external air temperature
7°C D.B./6°C W.B.;
D
t =
5°C.
Cooling (4)
outlet water temperature
7°C;
external air temperature
35°C
D
t =
5°C.