GENERAL TECHNICAL DATA
Size
030
045
050
Compressor
Type
°,A,P
type
Scroll
Scroll
Scroll
Compressor regulation
°,A,P
Type
On-Off
On-Off
On-Off
Number
°,A,P
no.
1
1
2
Circuits
°,A,P
no.
1
1
1
Refrigerant
°,A,P
type
R410A
R410A
R410A
Refrigerant charge (1)
°,A,P
lbs
9.0
11.9
13.0
Oil
°,A,P
Type
-
-
-
Total oil charge
°,A,P
lbs
-
-
-
System side heat exchanger
Type
°,A,P
type
Brazed plate
Brazed plate
Brazed plate
Number
°,A,P
no.
1
1
1
Minimum water flow rate
°,A,P
gpm
-
-
-
Maximum water flow rate
°,A,P
gpm
-
-
-
Hydraulic connections
Sizes (in/out)
°,A,P
Ø
1” 1/4
1” 1/4
1” 1/4
Connections (in/out)
°,A,P
Type
Gas femmina
Gas femmina
Gas femmina
Fan
Type
°,A,P
type
Axial
Axial
Axial
Fan motor
°,A,P
type
On-Off
On-Off
On-Off
Number
°,A,P
no.
2
2
2
Air flow rate
°,A,P
cfm
4,709
4,709
4,709
Sound data calculated in cooling mode (2)
Sound power level
°,A,P
dB(A)
70.5
70.5
70.5
Sound pressure level (10 m / 33 ft)
°,A,P
dB(A)
39.5
39.5
39.5
Sound pressure level (1 m / 3.3 ft)
°,A,P
dB(A)
55.4
55.4
55.4
Sound data calculated in heating mode (2)
Sound power level
°,A,P
dB(A)
-
-
-
Sound pressure level (10 m / 33 ft)
°,A,P
dB(A)
-
-
-
Sound pressure level (1 m / 3.3 ft)
°,A,P
dB(A)
-
-
-
(1) The load indicated in the table is an estimated and preliminary value. The final value of the refrigerant load is indicated on the unit’s technical label. For further information contact the office.
(2) Sound power calculated on the basis of measurements made in accordance with UNI EN ISO 9614-2. Sound pressure (cold functioning) measured in free field, 10 m / 33 ft away from the unit external surface (in compliance with UNI
EN ISO 3744).
ELECTRIC DATA
Size
030
045
050
Electric data
Peak current (LRA)
°
A
86.1
100.1
99.1
A,P
A
87.1
101.1
100.1
Minimum circuit amperage (MCA)
°,A,P
A
25.0
35.0
30.0
Maximum overcurrent permitted by the protec-
tion device (MOP)
°,A,P
A
40.0
50.0
50.0