SAFETY DEVICE TESTING
5-5
SSOV
ACTUATOR
COVER
SSOV
COVER
SCREW
Figure 5.6
SSOV Actuator Cover Screw Location
5.10 PURGE SWITCH OPEN DURING
PURGE
1. Set the unit’s
ON/OFF
switch to the
OFF
position. Place the unit in manual mode and
set the valve position between 25% and
30%.
2. Remove the air/fuel valve cover by rotating
the cover counterclockwise to unlock it and
then pulling it towards you. See Fig. 5.7.
3. Remove one of the two wires from the purge
switch (Fig. 5.8) and start the unit.
4. The unit should begin to start, then shut
down and display
PRG SWITCH OPEN
DURING PURGE.
5. Replace the wire on the purge switch and
depress the
CLEAR
button. The unit should
restart.
VALVE
COVER
Figure 5.7
Air/Fuel Valve Cover Location
5.11 IGNITION SWITCH OPEN DURING
IGNITION
1. Set the unit’s
ON/OFF
switch to the
OFF
position. Place the unit in manual mode and
set the valve position between 25% and
30%.
2. Remove the air/fuel valve cover (Fig. 5.7) by
rotating the cover counterclockwise to
unlock it then pulling it towards you.
3. Remove one of the two wires from the
ignition switch (Fig. 5.8) and start the unit.
4. The unit should begin to start and then shut
down and display
IGN SWITCH OPEN
DURING IGNITION.
5. Replace the wire on the ignition switch and
depress the
CLEAR
button. The unit should
restart.
Содержание KC Series
Страница 64: ......
Страница 74: ......
Страница 78: ......
Страница 86: ......
Страница 87: ...APPENDIX C Temperature Sensor Resistance Chart Balco ...
Страница 88: ......
Страница 91: ...APPENDIX E E 1 ...
Страница 100: ......
Страница 106: ......
Страница 112: ......
Страница 114: ......
Страница 117: ......
Страница 118: ......