AMR Integrated Water Heaters (Supplement to GF-146)
CHAPTER 11 – TECHNICAL DATA
CHAPTER 11:
TECHNICAL DATA
AMR Integrated Water Heater Technical Data
MODEL
DESCRIPTION
199
250
399
500
Category of discharge chimney
II and IV
II and IV
II and IV
II and IV
Maximum heat input
Btu/hr
199,500
250,000
399,000
500,000
Minimum heat input
Btu/hr
50,000
50,000
50,000
50,000
Turndown ratio
4:1
5:1
8:1
10:1
Number of burners
1
1
2
2
Gas fl ow rate (Natural gas)
ft3/hr
199.5
250
399
500
Gas fl ow rate (LP gas)
ft3/hr
80
100
160
200
Min / Max gas pressure (Nat. and LP)
In.W.C.
3 / 13
3 / 13
3 / 13
3 / 13
Min / Max water temperature
°F
68 / 180
68 / 180
68 / 180
68 / 180
Min / Max water pressure
PSI
8 / 160
8 / 160
8 / 160
8 / 160
Minimum water fl ow
GPM
0
0
0
0
Content of water
gal
33.7
34
35.4
36
Supply voltage / Frequence
120Vac 60Hz
120Vac 60Hz
120Vac 60Hz 120Vac 60Hz
Absorbed electric power (pump
l d d)
W
110
150
220
300
Air intake / Flue gas pipes diameter
inch
3
3
4
4
Max. length venting system
ft
120
120
120
120
CO (Carbon monoxide) with natural
ppm
<150
<150
<150
<150
CO (Carbon monoxide) with LP gas
ppm
<250
<250
<250
<250
NOx (0% O2 with natural gas)
ppm
<30
<30
<30
<30
CO2 (Carbon dioxide) for Natural gas
t hi h fi
%
8.4 to 8.7
8.8 to 9.1
8.4 to 8.7
8.8 to 9.1
CO2 (Carbon dioxide) for Natural gas
t l fi
%
8.4 to 8.7
8.8 to 9.1
8.4 to 8.7
8.8 to 9.1
CO2 (Carbon dioxide) for LP gas at
hi h fi
%
9.5 to 10
9.5 to 10
9.5 to 10
9.5 to 10
CO2 (Carbon dioxide) for LP gas at
l fi
%
10.5 to 11.5 10.5 to 11.5 10.5 to 11.5 10.5 to 11.5
O2 (Oxygen) for Natural gas at high fi
%
5.9 to 5.4
5.2 to 4.7
5.9 to 5.4
5.2 to 4.7
O2 (Oxygen) for Natural gas at low fi
%
5.9 to 5.4
5.2 to 4.7
5.9 to 5.4
5.2 to 4.7
O2 (Oxygen) for LP gas at high fi re
%
6.4 to 5.6
6.4 to 5.6
6.4 to 5.6
6.4 to 5.6
O2 (Oxygen) for LP gas at low fi re
%
4.8 to 3.4
4.8 to 3.4
4.8 to 3.4
4.8 to 3.4
Ionization current
uA (Micro
Amps)
4 to 7
4 to 7
4 to 7
4 to 7
Maximum flue gas temperature
°F
203
203
203
203
Maximum water condensate fl ow
GPM
0.032
0.039
0.064
0.077
Average acidity of condensation
PH
4
4
4
4
Heater weight - Empty of water / Full
f t
lb
211 / 411
216 / 428
312 / 607
323 / 623
Recovery Rating (100°F rise)
Gal/hr
227
285
455
570
DHW delivery (75°F rise)
GPM
5
6.3
10.1
12.7
OMM-0106_0A
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
37
of
52
GF-146-IR
Ph.: 800-526-0288