TROUBLESHOOTING
16. Shut down VFD power.
17. Turn On VFD power.
18. Set Pr. 59 to 1
19. Recalibrate the boiler using the combustion calibration procedures in Chapter 4.
Table 8-5. VFD Faults
NOTE
Check parameters 55, 56, 57, & 58 for the last 4 Trips.
VFD Fault
Possible Cause
U U
Low AC supply voltage
OU
High AC supply voltage
O.ht2
High ambient temperature
CL1
Analog input loss
(4-20 mA Air/Fuel Valve position signal)
EEF
Possible loss of parameters values
C.dAt
Empty SmartStick has been read
C.Err
Bad connection or faulty SmartStick
C.Acc
Bad connection or faulty SmartStick
8-15