APPENDIX K
K-1
BENCHMARK DUAL-FUEL
PROPANE SWITCH-OVER INSTRUCTIONS
Prior to operating a Benchmark Dual-Fuel Unit using propane, the Start and Stop levels must be
changed to 28% and 24%. In addition, the following valves must be set to the following
positions:
•
The Diverter Valve handle shown in Figure 1 must be set to the PROPANE (UP) position.
•
The Air Injection Valve handle shown in Figure 2 must be set to the Open position.
START/STOP LEVEL CHANGES
The Start and Stop levels are changed using the front panel controls on the C-More Control
Box. Proceed as follows:
1. Press the
MENU
key once.
Setup Menu
will be displayed.
2. Press the
▲
arrow key once.
Password
will be displayed.
3. Press the
CHANGE
key.
Password
will begin to flash.
4. Using the
▲
arrow key, increment the display and stop at
6817.
5. Press the
ENTER
key to store the displayed password.
6.
Password 2
will be displayed, indicating that the valid Level 2 password has been
stored.
7. Next, access the
Calibration Menu
by pressing the
MENU
key four times.
8. Press the
▼
arrow key one time.
Start Level 20%
should be displayed indicating that it
is currently set for Natural Gas operation.
9. Press the
CHANGE
key. The
Start Level
will begin to flash.
10. Press the
▲
arrow key and increase the
Start Level
to
28%.
11. Press the
ENTER
key to store the
28% Start Level.
12. Press the
▼
arrow key again.
Stop Level 16%
should be displayed indicating that it is
currently set for Natural Gas operation.
13. Press the
CHANGE
key. The
Stop Level
will begin to flash.
14. Press the
▲
arrow key and increase the
Stop Level
to
24%.
15. Press the
ENTER
key to store the
24% Stop Level.
16. Return to the
Operating Menu
by pressing the
BACK
key twice.
17. Refer to Figure 1 and verify that the Diverter Valve handle is set to the PROPANE (UP)
position.
18. Refer to Figure 2 and verify that the Air Injection Valve is Open
IMPORTANT
Remember to change the Start/Stop Levels back to 20% and 16%
prior to switching back to Natural Gas operation. Also, ensure that
the Diverter Valve handle is properly positioned as shown in
Figure 1 and the Air Injection Valve shown in Figure 2 is Closed.
Содержание GF-110 Benchmark Series
Страница 6: ......
Страница 8: ......
Страница 12: ......
Страница 32: ......
Страница 40: ......
Страница 46: ......
Страница 52: ......
Страница 58: ......
Страница 68: ......
Страница 76: ......
Страница 77: ...APPENDIX C C 1 Temperature Sensor Resistance Chart Balco ...
Страница 78: ......
Страница 84: ......
Страница 85: ......
Страница 86: ......
Страница 87: ......
Страница 88: ...APPENDIX F F 4 ...
Страница 89: ...APPENDIX F F 5 ...
Страница 90: ......
Страница 91: ......
Страница 92: ......
Страница 93: ...APPENDIX F F 9 ...
Страница 94: ...APPENDIX F F 10 ...
Страница 95: ......
Страница 96: ......
Страница 97: ......
Страница 98: ......
Страница 99: ...APPENDIX G G 5 ...
Страница 100: ......
Страница 101: ...APPENDIX H H 1 ...
Страница 102: ...APPENDIX H H 2 ...
Страница 104: ...APPENDIX H H 4 ...
Страница 105: ...APPENDIX H H 5 ...
Страница 106: ...APPENDIX H H 6 ...
Страница 108: ......
Страница 110: ...APPENDIX J J 2 P1 P2 P3 P4 P5 P6 BENCHMARK CONTROL PANEL REAR VIEW ...
Страница 112: ...APPENDIX K K 2 FIGURE 1 DUAL FUEL DIVERTER VALVE FIGURE 2 DUAL FUEL AIR INJECTION VALVE ...
Страница 115: ......
Страница 116: ......