2.5 Sub-menu Parameter Range and Default settings
Below is a list of the menu parameters with range and default settings. There is a table in the
previous section that provides a description of each parameter.
Cascade Sequencer Sub-Menu Parameter List
PARAMETER
UNITS
RANGE
FACTORY
BOILER SETTINGS
WATER HEATER SETTINGS
CUSTOM
Boiler address
/
0 …..16
0
0 - Stand Alone heater
1 – Master Heater
2 – 1st Dependent Heater
3 – 2nd Dependent Heater
4 – 3rd……etc
0 - Stand Alone heater
1 – Master Heater
2 – 1st Dependent Heater
3 – 2nd Dependent Heater
4 – 3rd……etc
Temperature
Unit
-
°C - °F
-
-
-
Cascade
Setpoint
°F
68..194
140
140
140
DHW ON..OFF
/
ON - OFF
OFF
ON (only if you want to drive
an indirect water heater)
OFF
Start delay time
sec
0 - 1200
600
600
15
Stop delay time
sec
0 - 1200
600
600
15
Start boiler diff
°F
0.9 - 22.5
5
5
5
Stop boiler diff
°F
0 - 45
2
2
2
Stop all boiler
°F
0 - 45
18
18
18
Max offset up
°F
0 - 36
18
18
18
Max offset down
°F
0 - 36
18
18
18
Rotation interval
Days
0 - 30
5
5
5
P Value
/
0 - 255
20
20
20
I Value
/
0 - 120
120
120
120
D Value
/
0..255
0
0
0
Slew rate
/
1 - 255
5
5
5
System
correction
°F
0 - 18
0
0
0
Mod delay factor
min
0 - 60
4
4
0