Aegis CZ20053 Скачать руководство пользователя страница 2

3.4  Operational Voltage: 230VAC/50Hz (Voltage Range: 

196 – 253 V)

3.5  Working Environment: Temperature: 0

~40

       Relative Humidity: ≤80%RH  
       Altitude: ≤2000 meter

3.6  Storage Condition: 

 Temperature: -20

~60

       Relative Humidity:  ≤75%RH
3.7  Product Size: 160mmx70.5mmx100

mm

3.8  Product Net 

Weight: About 500g

3.9  Standard 

Accessories:

 T

est Lead(1.5 meter)        1 pc

       Operating Manual             1 pc

 

       Carrying Case

 

                 

       1 set

CZ20053

RCD TESTER

4. Tester Description (See Figure 1, 2)

Figure  1

Figure  2

LCD Display

PHASE Button

I

n

 Button

TEST

 Button

Wiring LED Indicators

Rotary Switch

Test Terminals

T

est Lead

 Red (Live)

Green ( Earth )

 Blue ( Neutral )

5.

This instruction manual is subject 

t

o change without notice.

(1)

Test Measurements

Test Lead Connections

Insert 

the 

three plug connectors of test lead into 

the

 termin-

     als of the Tester. Red to L, Green to E, Blue to N. Then connect 

     the other end of the test lead into the tested circuit  

     (power socket 230V/50Hz).

Danger

● Do not touch any exposed metal or conductors during these

 

test

operations.

● Internal components in the tester may get hot during its

 

testing.

If the tester is operated continuously for a long time, it

 

may

cause damage to the unit or other hazards. It is

 not

recommended to use the tester for a continuous long period

 

of

time or continuous tests on production lines in RCD factories.

 

It

is only suitable for sampling precision tests.

● When using trip currents of 300mA or 500mA please allow 5

minutes between tests

.

 

To allow the tester to cool

.

6. Maintenance & Repair

6.1 Cleaning the Casing: 

Clean the surface of the tester with dry soft cloth; 

DO NOT USE

 

alcohol 

or 

solvent

s as

 it may cause corrosive damage to the LCD.

 

Protect the test instrument from any moisture.

6.2 Repair

 Please contact your Aegis sales representative if the following 

 issues occur:

A. The test instrument’s casing is broken or the components are

damaged.

B. LCD display works abnormally.

C. Unexpected data occur under normal use.

D. The buttons do not function normally.

E. Noise occurs during tests.

(4) Taking RCD Tests

4.1 Set the rotary switch to test parameters

● Non-Tripping -------------------×1/2: Max. trip time up to 1000ms;

● Tripping -------------------------×

1: Ma

x

. trip time up to 1000m

s

 (E

xc

ept

500

mA);

● Tripping -------------------------×

1(500mA): Ma

x

. trip time up to 300m

s;

● Fast Tripping------------------- ×5 (only 10, 20, 30mA ): Max. trip time

up t

o 1000ms;

AUTO RAM

Te

s

t: 20

%

~110

%

 o

f

 rated trip 

curre

nt

(I

n), Max. trip time up to 300ms.

4.2 Press TEST button

● Non-Tripping Test -------The RCD should not trip.

● Tripping --------------------The RCD should trip.

● ×5 Fast Tripping: ----------- The RCD should trip.

● AUTO Ramp Test: ---------- The RCD should trip, trip time and

 

trip

current are displayed simultaneously

4.3 

P

re

ss

 

P

HASE (0 /

18

0 ) button to 

s

et the 

phas

e angle and repeat 

      4.2 to determine the fastest trip time.

4.4 Press PHASE to change the phase angle and repeat 4.2

4.5 When the tests are finished, disconnect the test lead from the  

      tested circuit immediately.

(2) Wiring Check

Check the wiring status by identifying three LEDs. If P-E and P-N

green LEDs are illuminated an

d

 red LED is off, it indicates the

wiring is correct. Otherwise wiring is wrong due to reverse

connection between L and N terminals or bad grounding. Please

unplug the test leads, check and correct the relative circuits until

correct wiring LED indication is

 obtained.

(3)

Press I

n button to adjust the trip current(I

n) to the same

current rating as the RCD that is under test. The set trip current

will be shown on lower part of LCD.

 Default value: I

n----------------- 30mA

0 /180 ----------- 0

Caution:

 Reverse connection between L and N terminals during

wiring 

c

he

ck

 may 

c

au

s

e RCD to trip

. P

lea

s

c

he

ck

 and 

c

orre

c

t

the circuits until the wiring indication is obtained before you

proceed to next operation.

Danger

    Do not proceed into the test (press TEST button) if the 

    wiring is incorrect, otherwise it may cause error to the result or 

    other hazards.

AEGIS

CZ20053-DRW02-02 

RCD Tester User Guide

AEGIS

200 Rooks Road

 

V

ermont, VIC

Australia 3133

T

oll free: 1300 723 447

 

T

el: (61 3) 8872 6666

 

Fax: 1300 123 447

E-mail: [email protected]

www

.aegis.net.au