RCD Tester
1. Safety Instructions
This operating manual includes the operation guidance and safety
instruction when using the CZ20053 tester. Please read before use.
Caution
●
Before using the tester, please read and understand the operating
manual.
●
●
Keep the operating manual intact, and accessible for
reference
during the process of testing.
W
hen using the tester, operator must follow the
testing
procedure as mentioned in the operating manual.
●
Carefully read the operating manual regarding the safety information.
● Ensure you follow all the related safety
instructions, otherwise it
may cause accidents or damage the teste
r.
Safety sign “ ” has three meanings in this manual, user needs to
pay attention to the sign “ ”.
Danger
-----identifies conditio
n
s and actions that most likely
pose severe or fatal hazard(s)
.
Warning---identifies conditio
n
s and actions that may pose
severe or fatal hazard(s)
Caution---identifies conditions and actions that may cause
minor injury or damage to the tester.
Danger
● T
his test instrument is only suitable to use on single phase
c
ir
c
uits,
230V+10%-15%. (Operational V
oltage Scope: 196 – 253 V)
● T
o avoid potential ele
ct
ri
c s
ho
ck
or personal inquiry, do not use
the test instrument or test leads if they appear damaged or have
exposed metal parts. If test instrument is not operating properly
or in doubt, please have the instrument serviced.
● Do not touch any part of the test lead w
hile the test instrument is
testing.
● Remove the test leads away from the power circuit after the
tests are completed. Do not keep the test leads connected to the
power circuit after the tests are completed.
W
arning
● Do not open or disassemble the tester during the test
measurements. The high voltage prese
nt in the tester may
endanger the user. If tester needs
servicing
or repairing, please
contact
your
Aegis service agent.
●
If the test instrument appears abnormal (for example LCD
displaying
incorrec
tly,
incorrec
t
calcula
tion, housing damage, noise
issue during measurements et
c
.). Please
con
t
ac
t your
A
egis
service agent.
● Do not use the tester if your hands are wet.
Caution
● E
nsure the test lead probe (use onl
y A
egis spe
c
ified test leads)
are inserted into the
corresponding
port in order to provide a
safe measurement. It is not recommend
ed to use third party
test lead probe on the CZ20053 tester.
● Do not expose the tester to extreme temperatures and wet env
ironment.
● Soft cloth and mild detergent should be used to clean the surface of
the tester
. No abrasive and solvent should be used when servicing.
● If wet, dry the tester before storing it.
This test instrument has the following signs, please pay attention to
the content when using.
danger, warning, caution
double or reinforced insulation
Grounding
2. Features
●
Suitable for Use
on 230V/50Hz single-phase line (operating
voltage: 196~253V);
●
Micro Processor IC
to maintain high accuracy, reliability
and stability;
●
Wiring Check:
Three – LED indication
When P-E and P-N green LEDs are illuminated and red LED is
off, the wiring is correct. Otherwise it indicates wiring (P and N
are reversed or bad grounding) is incorrect.
●
Phase Angle Selection:
The tests can be performed at positive
0 or negative 180 phase angles.
●
Over-Load Indication:
“OL mS” shows when trip time exceeds
Max. test time
●
Auto Data Hold:
The test results will be maintained for a while after
the tests have been completed.
3. Technical Specifications
3.1 Measuring Range & Accuracy. (Temperature: 23±5
℃
; Humidity:
45%~75% RH; Altitude ≤2000m)
CZ20053:
Functions Voltage(AC)
Trip Current( I
△
n
)
Trip Time
(MAX)
Accuracy
Trip Current Trip Time
X 1/2
X 1
X 5
AUTO
RAMP
TEST
230V
(Tolerance:
-15%~+10%)
Frequency:
50Hz
10 / 20 / 30 /100
/ 300 / 500mA
10 / 20 / 30mA
500mA
10 / 20 / 30 /100 /
300 mA
10 / 20 / 30 /100 /
300 / 500mA
1000mS
1000mS
300mS
(RAMP
increase to
10%) I
△
n
from
20%~110%
300*10 mS
1000mS
Tolerance:
-10%~0%
Tolerance:
0%~+ 10%
Tolerance:
-10%~+10%
±0.6% rdg
±4dgt
3.2 Measuring Range (Functions)
×1/2--------------------Non-trip test, check RCD sensitivity
×1----------------------Measure trip time
×5----------------------Measure fast trip time at I
△
n×5 trip current
AUTO RAMP Test---- Measure trip current
3.3 Application Standard:
A
S
61010
.1
CAT III 300V, Pollution
Degree 2
I
EC 61010-2-31
AS
/NZS
CISPR 11
●
Auto Ramp Test:
Test the trip current and trip time
simultaneously.
●
Power-Off Warning Indication:
The internal buzzer will alarm after
operating greater than 3 minutes.
●
Power Save and Environment-Friendly:
Powered directly by
the tested circuit (Power 230V/50Hz). No need to use batteries;
●
Fused Protection
●
Double or Reinforced Insulation for safe design.
AEGIS
CZ20053