5. installation
5.1 insidE PRotEct PV 4600 PackagE
The following items are included in your Protect PV 4600 Package:
(1) Protect PV 4600 PV-Inverter
(2) Installation and Operation Manual
(3) 4 Mounting Screws and 4 Blade receptacle
(4) 2 Safety-lock screws
(5) 3-hole Rubber Bushing
(6) Mounting Bracket
5.2 mounting youR PRotEct PV 4600
sUggestions befoRe MoUnting
To obtain optimal results from your PV-Inverter, please consider the
following guidelines before installing the device:
Do not expose the PV-Inverter to direct sunlight. Direct sunlight increa-
ses the internal temperature that may reduce conversion efficiency.
- Check the ambient temperature of installation is within specified range
-20 ~ +55 °C.
- The AC grid voltage is between 196 and 253 VAC, 50/60 Hz.
- Electric utility company has approved the grid connection.
- Qualified personnel are performing the installation.
- Adequate convection space surrounds the inverter.
- Inverter is being installed away from explosive vapors.
- No flammable items are to be near the inverter.
Protect PV can be installed and operated at locations where the am-
bient temperature is up to 55 °C. However, for optimal operation, it is
recommended that Protect PV is installed where the ambient tempera-
ture is between 0 ~ 40 °C.