25
4.4.2
Display
Explanations
1. OFF - Pushbutton
2. ON / Alarm off - Pushbutton
3. Orange LED bypass
4. Green LED inverter
5. Orange LED for battery mode (Battery)
6. Green LED for net state (Line)
7. - 11. Bar graph LEDs for UPS battery utilization resp.
capacity (remaining autonomy time)
7. LED load (0-35%)
battery capacity (81-100%)
8. LED load (36-55%)
battery capacity (61-80%)
9. LED load (56-75%)
battery capacity (41-60%)
10. LED load (76-95%)
battery capacity (21-40%)
11. LED load (96-105%)
battery capacity (0-20%)
12. LED for battery problem
You will find detailed explanations of the displays on page 43.
1
2
3
4
5
6
7
8
9
10
11
12
Содержание PROTECT C. 10000
Страница 1: ...OPERATING INSTRUCTIONS UPS PROTECT C PROTECT C 6000 S PROTECT C 10000 S ...
Страница 19: ...20 3 5 Certification ...
Страница 23: ...24 4 4 Overview Connections Operating Display Elements 4 4 1 Front view PROTECT C 6000 S PROTECT C 10000 S ...
Страница 25: ...26 4 4 3 Rear view connections PROTECT C 6000 S PROTECT C 10000 S ...