General data
Classification
VFI SS 211 acc. to IEC 62040–3
Double conversion technology
Overall efficiency AC-AC (full load)
PROTECT C. 1000 (S)
85 %
PROTECT C. 2000 (S)
85 %
PROTECT C. 3000 (S)
88 %
Noise level (1m distance)
PROTECT C. 1000 (S)
< 45 dB (A)
PROTECT C. 2000 (S)
< 50 dB (A)
PROTECT C. 3000 (S)
< 50 dB (A)
Type of cooling
Forced cooling
by variable speed fans
Operating temperature range
0°C to +40°C
Recommen15°C to
+25°C (due to battery
system)
Storage temperature range
0°C to +40°C
Relative humidity
< 95%, non-condensing
Max. site altitude
up to 1000 m above sea level
If the UPS is installed or used
in a place where the altitude is
above than 1000m, the output
power has to be reduced:
Outlets
PROTECT C. 1000 (S)
4 x IEC 320-10A
PROTECT C. 2000 (S)
6 x IEC 320-10A
PROTECT C. 3000 (S)
4 x IEC 320-10A
+ 1 x IEC 320-16A
Equipment colour
Black line
Altitude (m)
1000
1500 2000 2500 3000
Derating Power
100%
95%
90% 85% 80%