If you have already taken the UPS into operation then switch it off as 
the first step. Now disconnect the UPS from the mains by 
disconnecting the mains connector. 

¾

  Before you perform the installation described below, make sure 

that none of the cables are live. 

¾

  Make sure that the external bypass switch is in its default 

position "NORMAL". 

        zum
USV Ausgang

O

u

tput

O

u

tput

O

u

tput

O

u

tput

    Fuse
250V/10A

    Fuse
250V/10A

    Fuse
250V/10A

    Fuse
250V/10A

Netzeingang

AC Input

to UPS Output

        zum
USV Eingang

to UPS Input

Ausgang

Output

 

 

Rear view of MBS 6000 

 

{

 Connect the input of the external bypass to the mains 

connection cable provided with the UPS and plug the mains 
connector into a suitable shockproof socket. In particular for 
types with high power ratings, make sure that the fuse in your 
sub-distribution system is sufficiently large. 

|

  Two connection cables are supplied with the external bypass. 

Make the following connections: 

Connect "OUTPUT" to the UPS output. 

}

  Connect "INPUT" to the UPS mains input. 

~

  As the last step, connect your loads. To do this, use the load 

connection cables provided with the UPS. 

This completes the installation and cabling of the UPS with the 
external bypass unit. Now start up the UPS system in accordance 
with the operating instructions. 

Содержание MBS 6000

Страница 1: ...einheit für USV PROTECT C 6000R External Bypass Unit for UPS PROTECT C 6000R Typ Type MBS 6000 AEG Power Solutions GmbH Änderung Revision 01 Schenuit Schneider Datum Date 09 07 2009 Operating instructions 8000019069 BAL en ...

Страница 2: ...ible for the loads to be supplied directly from the MBS 6000 LEDs with various colours clearly signal which operating status has been selected Scope of delivery External bypass unit MBS 6000 2 connection cables to the UPS Operating instructions Prerequisite AEG UPS in the PROTECT C 6000R series Technical data Nominal connection voltage frequency 230 VAC 50 60 Hz Nominal current 32 A Number of outp...

Страница 3: ...ion bypass position i e load supply directly from the mains additional complete isolation of the UPS Attention UPS output may still be live due to its internal voltage source If there is a mains failure during TEST and BYPASS operation then the supply to the connected loads will be interrupted IMPORTANT UPS must be switched to BYPASS operation if external bypass switch will be operated refer to th...

Страница 4: ... Output Rear view of MBS 6000 Connect the input of the external bypass to the mains connection cable provided with the UPS and plug the mains connector into a suitable shockproof socket In particular for types with high power ratings make sure that the fuse in your sub distribution system is sufficiently large Two connection cables are supplied with the external bypass Make the following connectio...

Страница 5: ...5 5 Wiring diagrams UPS operation Service position Manual bypass NORMAL TEST BYPASS ...

Страница 6: ...no Date of purchase Dealer stamp Signature Errors and changes excepted Emil Siepmann Straße 32 59581 Warstein Belecke Germany Tel 49 0 180 523 4787 Fax 49 0 180 523 4789 www aegpartnernet com Operating instructions 8000019069_01 BAL en ...

Отзывы: