3 Installation
IST Series UPS (10kVA-200kVA)
User Manual
26
Avoid any object block the ventilation hole on the front panel and rear panel, which is to
keep good ventilation for the UPS, or, it may rise the inner temperature, even influence
the UPS service time.
3.2.4 Selection for Input and Output Wires
For the wire sectional area selection of AC input and output wires, please refer to Table3-1
and Table3-2 for corresponding recommended values, and choose upwards.
Table3-1
Recommended wire and terminal specification 1
Model
Item
10kVA 20kVA 30kVA 40kVA 50kVA 60kVA
M
a
in
s i
n
pu
t
Mains input current (A)
25
40
55
71
95
111
Recommend
ed
wire
sectional area
(mm
2
)
U/V/W/N
4×4
4×10
4×16
4×16
4×25
4×35
Wire terminal model
DT4
DT10
DT16
DT16
DT25
DT35
B
yp
as
s i
n
p
ut
Bypass input current (A)
15
30
45
61
76
91
Recommend
ed
wire
sectional area
(mm
2
)
U/V/W/N
4×2.5
4×6
4×10
4×16
4×16
4×25
Wire terminal model
DT2.5
DT6
DT10
DT16
DT16
DT25
O
u
tp
u
t
Output current(A)
15
30
45
61
76
91
Recommen
ded
wire
sectional
area (mm
2
)
U/V/W/N (when
the load is non-
linear load, the
N wire should
increase
the
wire sectional
area)
4×2.5
4×6
4×10
4×16
4×16
4×25