27
!
For contractors
• Observe the type plate (
A
18).
• See "5.1 Specification".
The specific electrical resistant of the water used must not fall below that stated on the type plate. In a
linked water network, observe the lowest electrical water resistance (see "5.2 Application areas"). Your
water supply company will advise you of the specific electrical water resistance or conductivity.
• Install the device only in an enclosed room free from the risk of frost. Store the dismantled device in a
room free from the risk of frost, as water residues remain inside the device.
• The protection IP 25 (hoseproof) can only be ensured with a correctly fitted cable grommet.
•
Water installation
:
– Cold water line material:
Steel, copper or plastic pipework.
– DHW line material:
Copper or plastic pipework*.
* The instantaneous water heater can reach operating temperatures up to 60 °C. In case of faults, loads
up to 95 °C / 1.2 MPa can occur temporarily in the installation. Any plastic pipework used must be suitable
for these conditions.
• A safety valve is not required.
• Never use taps/valves for open vented equipment.
• For thermostatic valves, see "1.6 Recommended adjustment".
•
Electrical installation:
• Use only permanently wired power cables.
• The equipment must be able to be separated from the mains power supply, for example by fuses that
disconnect all poles with at least 3 mm contact separation.