ST3 6-10kVA Service Manual Rev.1 

Allis Electric                                                      Page 4 of total 12                                    September 2006

 

3. Troubleshooting

 

 

3.2 PFC Analysis: 

In this section, some components you could check to see if failure occurs on PFC Correction circuit as shown below. Be 
aware of F301, F302 fuse open indicates failure of this block. Please replace all faulty components before re-start the UPS. 

6/10kVA-PFC-Right side 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

6/10kVA-PFC-Left side 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Step 

Checked components 

Instrument 

function 

Reference 

Value 

Failure Mode 

F301, F302 

 0 

 Open 

(A, K) 

 2.6 

M

 

Short or open 

Q301 
Q302

 

(G, K) 

 10 

 

Short or open 

 

 
 

Action ltem:

 If all above-stated components are replaced well and UPS still can’t work, change the PFC 

IGBT driver module. 

Содержание Star T3

Страница 1: ...Service Manual STAR T3 T3R UPS 6kVA 10kVA 220VAC www allis com tw...

Страница 2: ...PSDR Right side 1 1 2 6 10 kVA PSDR Left side 1 2 Fault and Warning 2 3 Troubleshooting 3 3 1 Quick Start 3 3 2 PFC Analysis 4 3 3 Boost Analysis 5 3 4 Inverter Analysis 7 3 5 Charger Module Analysis...

Страница 3: ...Electric Page 1 of total 13 September 2006 1 PSDR Introduction 1 1 6 10 kVA PSDR Right side c d e f 1 2 6 10 kVA PSDR Left side f e d 1 Bypass Mosfet Driver 2 Inverter IGBT Driver Module 3 Boost IGBT...

Страница 4: ...nverter Fail 1 Inverter circuit failed 2 Inverter driver failed 3 PFC circuit failed 1 Replace the Inverter components or driver 2 Replace the PFC components or driver Fault Warning Normal y UPS in No...

Страница 5: ...6 D303 D305 D307 Push Pull Boost D309 D311 D308 D310 Power Diode Short or open Q201 Q202 Q203 Q204 IGBT C E short or open D201 D202 D203 D204 D205 Inverter D210 D211 D212 D213 Power Diode Short or ope...

Страница 6: ...ware of F301 F302 fuse open indicates failure of this block Please replace all faulty components before re start the UPS 6 10kVA PFC Right side 6 10kVA PFC Left side Step Checked components Instrument...

Страница 7: ...bleshooting 3 3 Boost Analysis 6 10kVA Boost Right side 6 10kVA Boost Left side Step Checked components Instrument function Reference Value Failure Mode E C 800k short 1 Q306 Q311 G E 15 8k short or o...

Страница 8: ...ember 2006 4 R325 R331 R334 R342 R337 R328 10 open 5 R390 R388 R389 R393 R392 R391 2 2 open 6 F303 F304 0 open A K 2 5M short 7 Q305 G K 10 short Action ltem If all above stated components are replace...

Страница 9: ...de Step Checked components Instrument function Reference Value Failure Mode E C 100k Short 1 Q201 Q202 Q203 Q204 G E 23 5k Short or Open 2 D201 D202 D203 D204 D205 Diode 0 36V 0V 3 D210 D211 D212 D213...

Страница 10: ...Analysis 6 10 kVA Charger Module Long back up type Step Checked components Instrument function Reference Value Failure Mode 1 F1 0 open E C 1M 2 Q301 Q105 G E 10k 3 D303 DIODE 0 4V 0V 4 R315 10 open...

Страница 11: ...f total 12 September 2006 6 10 kVA Charger Module Standard type Step Checked components Instrument function Reference Value Failure Mode 1 F901 F902 F903 F904 F905 F906 0 open S D 1 7M 2 Q907 Q908 G S...

Страница 12: ...3 6 PFC Boost Inverter IGBT Driver Module Analysis 6 10kVA Boost Right side 6 10kVA Boost Left side Step Checked components Instrument function Reference Value Failure Mode ZD201 V 0 7V 0V Q201 Q202 V...

Страница 13: ...AT Press the switch on front panel for more than 3 seconds you will see current limit for a short time on the DC power supply for about only 2 seconds then UPS should be DC start If UPS does not start...

Страница 14: ...tep 3 If the UPS re start normally check the DC_BUS and output voltage For 6 10kVA DC_BUS 340 350 and 340 350VDC deviation between negative and positive voltage should be within 10VDC Output Voltage 2...

Страница 15: ...t with AC power source then follow the step3 and step4 to check the DC_BUS and output voltage again Also the charger voltage need to be confirmed the charger voltage should be 274VDC 1 If UPS fails to...

Отзывы: