2 Overview 

AEC UPS IST7 10-30 KVA 

User Manual 

 

64 

 

Close the total output breaker of load. 

After the parallel system turns to bypass power supply, close the total output breaker of load, system 

bypass supplies power for load. 

Start each UPS successively, the system turns to inverter power supply. 

2.4.2 Shutdown Parallel System 

 

If  the system  bypass is normal,  after shutting down  the UPS,  the system  will  turn to  bypass power 

supply mode; if the system bypass is abnormal, after shutting down the UPS, the system will turn to 

no output mode, the system output is outage. 

Before shutting down, please ensure that load is closed and can endure the status of power outage at 

any time. 

Close the load of parallelsystem, keep the UPS run without load for 5min to eliminate inner heat. 

Perform UPS Shutdown to close all UPS, system turns to bypass power supply. 

Disconnect the load total breaker, each UPS output breaker (OUTPUT), battery breaker, battery breaker (BYPASS), 

mains input breaker (POWER) successively. 

 

 

If  it  just  needs  to  close  the  UPS,  system  turns  to  bypass  power  supply  and  the  load  without  power 
outage, just perform 0; if it needs to power off all UPS system, perform all above steps. 

2.4.3 Emergency Power Off (EPO) 

Single UPS running 

Press the EPO button of the UPS or the EPO button of total system, the UPS will shut down and close 

all output. 

Multi UPS running in parallel system 

 

EPO linkage is enabled 

Press the EPO button of the UPS or the EPO button of total system, all the paralleled UPS will 

shut down and close all output. 

Содержание IST7 20kVA

Страница 1: ...User Manual AEC UPS IST7 The NEW high frequency Three Phase 10kVA 30kVA...

Страница 2: ......

Страница 3: ...to prompt users to comply with safety matters during installation operation and maintenance Safety symbol meaning as follows Symbol Description Alerts you to a high risk hazard that could if not avoi...

Страница 4: ...nd Maintenance Requirements 6 1 3 Environment Requirements 7 2 Overview 8 2 1 Product Intro 8 2 1 1 Product Features 8 2 2 Work Principle 9 2 2 1 Work Principle Diagram 9 2 2 2 Work Mode 10 2 3 Appear...

Страница 5: ...39 3 5 1 Check Electrical Connection 39 3 5 2 UPS Test 40 3 5 3 Connect Load 40 4 Touch Screen Operation and Setting 41 4 1 Menu Hierarchy 41 4 2 MainPage 42 4 3 System Work Status Display 43 4 4 Moni...

Страница 6: ...s Mode From Inverter Output 67 5 3 6 Switch to Inverter Output from Maintenance Bypass 68 5 3 7 Emergency Power Off EPO 68 5 3 8 Emergency Power Off Recovery 69 5 4 Parallel SystemStartup and Shutdown...

Страница 7: ...AEC UPS IST7 10 30 kVA User Manual Foreword v 7 Package Transportation and Storage 79 7 1 Package 79 7 2 Transportation 79 7 3 Storage 79 A Technical Specifications 80 B Acronyms and Abbreviations 84...

Страница 8: ......

Страница 9: ...ion instructions in this section carefully which is to avoid accident The DANGER WARNING CAUTION in the manual are not all the safety announcements that you must abide by there are just the supplement...

Страница 10: ...it is strictly prohibited to perform high voltage and AC operation as well as in the tower or the mast The atmosphere will generate a strong electromagnetic field in a lightning storm Therefore in ord...

Страница 11: ...e product is class C3 device If the product is used in resident living it may cause wireless interference User should take actions to avoid the interference Warning label should be affixed away from U...

Страница 12: ...neously or it may cause battery damage or human injury Prevent electrolyte leaking from batteries The metal objects and circuit board will be corroded by the overflowing electrolyte and it will result...

Страница 13: ...is dangerous high voltage contacting by accident may lead to deadly danger So when measure with electricity it is necessary to do the protection such as wear insulated gloves etc The measure meter mu...

Страница 14: ...nance please disconnect the AC power and battery to isolate the power input It is better to measure the input output and battery terminal bars by a voltmeter to ensure the input power is disconnected...

Страница 15: ...like this please consult the manufacturer in advance 1 3 Environment Requirements The used environment may influence the service life and reliability of the device So please avoid using the device in...

Страница 16: ...zed DSP to control the inverting phase synchronization output current sharing logic of the power unit which is with high precision high speed and perfect whole system performance Energy conservation a...

Страница 17: ...r falling mass impulse static discharging surge etc The excellent EMC characteristics can completely filter each power grid interference and also decrease and eliminate the interference of UPS itself...

Страница 18: ...wn Before battery discharge completely if mains recovers the rectifier will switch to mains input and charge battery at the same time During the switch between grid power supply and battery power supp...

Страница 19: ...ly for load cannot be interrupted user can shut down the inverter and make the UPS works in bypass status then switch on the maintenance bypass breaker and switch off the mains pint breaker and bypass...

Страница 20: ...y On red rectifier abnormal DC AC indicator On green inverter works normally On red inverter abnormal BYP indicator On green bypass output On red bypass abnormal BATT LOW indicator On red battery is l...

Страница 21: ...ta trovata Errore L origine riferimento non stata trovata Figure1 2 Structure layout diagram of 10kVA 30kVA open front door The dots in above figure are the wiring bundling slots which are used for fa...

Страница 22: ...function illustration NO Silk screen Signal Function illustration 1 ND9 It can be set to battery grounding When the signal is valid NO and COM is short circuited 2 ND10 3 ND11 4 ND12 Reserved When th...

Страница 23: ...ND2 Mains FAIL signal When the signal is valid COM and NO is cloased COM and NC is opened The allowable voltage withstand is 250V 1A 3 ND3 BAT LOW signal When the signal is valid COM and NO is cloased...

Страница 24: ...em communication abnormal Maintenance bypass is on Buzzer beeps apace the red BATT LOW indicator on It is not allowed to supply power by battery or charge battery Battery over voltage Battery circuit...

Страница 25: ...normal The communication of cabinet inner busbar 3 abnormal BSC synchronization wire abnormal Battery low temperature alarm The static startup is not allowed PFC software version is inconformity INV s...

Страница 26: ...ack phase Mains over current Mains current DC component is too large It turns to float charge The charge current limiting value is 0 05C Battery high temperature alarm Charge is not allowed Battery ov...

Страница 27: ...he UPS should be installed by authorized person who is special trained and achieve the qualification of high voltage and AC power The UPS is just suitable for installing on the concrete or nonflammabl...

Страница 28: ...2 Overview AEC UPS IST7 10 30 KVA User Manual 20 3 2 Installation Preparation 3 2 1 Installation Tools Tools...

Страница 29: ...ounding wire should not exceed 5V Before installation please ensure that the AC input voltage and mains input wire capacity meet the UPS requirements And considering if there has current carrying capa...

Страница 30: ...istribution circuit is configured with a bipolar disconnecting switch 3 2 3 Installation Space Maintain a clearance of at least 800mm from the front panel side pane or rear panel of the UPS to the wal...

Страница 31: ...sectional area mm2 U V W N 4 10 4 16 Wire terminal model DT10 DT16 Bypass input Bypass input current A 30 45 Recommended wire sectional area mm2 U V W N 4 6 4 10 Wire terminal model DT6 DT10 Output Ou...

Страница 32: ...Reverse Feedback Protection Optional It is suggested to add the contactor with 220V AC coil at the AC power distribution side as the reverse feedback protection device 3 3 Transportation and Unpacking...

Страница 33: ...xternal package remove the foam pad and plastic bag and take out the accessories Check the UPS Inspect the appearance of the UPS and check if there has any damage caused by transportation If any damag...

Страница 34: ...s of the UPS are the same In above figure we take 80kVA 120kVA UPS as an example to illustrate Loosen the brake of all the wheels or heighten the 4 supporting feet as shown in Figure1 8 The wheels of...

Страница 35: ...d tilting even device damage Put the tilting plate to the front of the UPS and keep the higher end of the sliding plate close to the wooden bracket and move the UPS to ground slowly as shown in Figure...

Страница 36: ...ento non stata trovata and installation clearance requirement see 3 2 3 Installation Figure1 10 Size of 10kVA 40kVA Push the UPS to the installation site During moving the UPS to the ground please mov...

Страница 37: ...g Open the front door of the UPS remove the bottom wiring cover plate as shown inFigure1 12 The battery and neutral wire terminal of 10kVA 30kVA are all at the back of the UPS so before wiring it need...

Страница 38: ...ire hole are as shown in Figure1 1 Errore L origine riferimento non stata trovata Errore L origine riferimento non stata trovata and connect the cables according to Figure1 2 Errore L origine riferime...

Страница 39: ...put wire and input out terminal is reliably avoid bad connection or wrongly connection It is suggested to select DC breaker for battery DC input the detail wiring is as shown in Figure1 3 Figure1 3 Ba...

Страница 40: ...e wash the contact part with plenty water and go to hospital immediately To avoid electric shock and short circuit while replacing battery pay attention to following precautions Do not wear watch ring...

Страница 41: ...the wiring of cabinet is firmly Yes No 3 Check if the safety id of AC power distribution unit is complete Yes No 4 Check if the wire connection point is firmly Yes No 5 Check if the battery is connect...

Страница 42: ...starting mode generator charging output charger power setting generator battery low voltage start point Generator configuration Function setting Timing self dedusting Regular dedusting period forced d...

Страница 43: ...n flickers and shows as System mains input When mains input abnormal the icon flickers and shows as Battery status When battery abnormal the icon flickers and shows as System output When output abnorm...

Страница 44: ...zing shutdown exit parallel system maintenance bypass output bypass output battery inverter output mains inverter output grid connected aging ECO bypass output frequency conversion INV output aging by...

Страница 45: ...AEC UPS IST7 10 30 kVA User Manual 2 Overview 37 Figure1 6 Exit parallel system Figure1 7 Maintain bypass output Figure1 8 Bypass output...

Страница 46: ...2 Overview AEC UPS IST7 10 30 KVA User Manual 38 Figure1 9 Battery INV output Figure1 10 Mains INV output Figure1 11 Grid connected aging...

Страница 47: ...AEC UPS IST7 10 30 kVA User Manual 2 Overview 39 Figure1 12 ECO bypass output Figure1 13 Frequency conversion INV output Figure1 14 Aging bypass output...

Страница 48: ...lick the warning indicator it will show the current fault as shown in Figure1 16 Figure1 16 Current fault window 4 4 Monitor Function 4 4 1 Bypas Input Information In main page click icon it will ente...

Страница 49: ...e current system mains three phase voltage current and frequency Figure1 18 Mains information 4 4 3 Battery Information In main page click icon it will enter battery information page In the page it sh...

Страница 50: ...version status battery charge 4 4 4 System Output Information Page In main page click icon it will enter system output information page as shown in Figure1 21 In the page it shows the current three ph...

Страница 51: ...ecord 10000 pieces information at most When the record exceeds 10000 piece the earliest information will be covered by new one All records is ranked in inverted order of time 1 1 1 Event Log In inform...

Страница 52: ...og page as shown in Figure1 24 This page shows the user parameter setting record Figure1 24 User log 1 1 3 Device Information In information query page click device information icon it will enter prod...

Страница 53: ...User Manual 2 Overview 45 Figure1 26 Product information 2 Figure1 27 Product information 3 Figure1 28 Product information 4 Setting Management In main page click icon it will enter user login page a...

Страница 54: ...g page as shown in Figure1 30 Common user can look up the parameters but cannot set the parameters Maintenance staff can look up and set each parameter Figure1 30 Setting management page 1 2 1 System...

Страница 55: ...tem setting Figure1 1 System setting page 1 Figure1 2 System setting page 2 If setting successfully at the right of the parameter will show mark as shown in Figure1 3 If setting failure it will show m...

Страница 56: ...k Bypass Setting it will turn to bypass setting page as shown in Figure1 1 Click enter box to change the parameter Click Save button to save the setting The marks of setting success and setting failur...

Страница 57: ...save the setting The mark of setting success and setting failure is the same as that of system setting Figure1 1 ECO setting 1 2 2 Battery Management In setting management page click battery manageme...

Страница 58: ...2 Overview AEC UPS IST7 10 30 KVA User Manual 50 Figure1 2 Battery setting page 2 Figure1 3 Battery setting page 3 Charging setting Figure1 1 Charge setting 1...

Страница 59: ...er Manual 2 Overview 51 Figure1 2 Charge setting 2 Figure1 3 Charge setting 3 1 2 3 Battery Test In setting management page click battery test icon it will enter battery test page as shown in Figure1...

Страница 60: ...ave button to save the setting The mark of setting success and setting failure is the same as that of system setting Generator setting Figure1 1 Function configuration page Dedusting setting When the...

Страница 61: ...AEC UPS IST7 10 30 kVA User Manual 2 Overview 53 1 2 5 HMI Setting In setting management page click HMI setting icon it will enter HMI setting page as shown in Figure1 2 Figure1 2 HMI setting...

Страница 62: ...e1 3 The password is the Arabic numerals from 1 place to 6 places After modifying click Confirm button to perform the modification Figure1 3 Password setting Buzzer Control When unit or system abnorma...

Страница 63: ...User Manual 2 Overview 55 Figure1 4 Confirm to power on While powering off click button it will enter the ON OFF page as shown in Figure1 5 click OK button to perform the shutdown operation Figure1 5...

Страница 64: ...the load first When mains power outage if the UPS is power supplied by generator it is necessary to start the generator firstly After the generator work stably the UPS can be connected or it may cause...

Страница 65: ...voltage of negative battery group should be less than 11 5 battery amount and pay attention to the polarity avoid wrong battery connection Ensure that the auxiliary contact of battery breaker is conne...

Страница 66: ...status chart and ensure if the system turns to inverter to supply power During testing ensure that the UPS three phase output voltage and frequency is normal through the real time data in the touch sc...

Страница 67: ...e power supply for load will break off Shut down the UPS inverter please see 2 3 3 UPS Shutdown The UPS can be shutdown by touch screen or OFF combination button on the panel System will turn to bypas...

Страница 68: ...maintenance it is strictly forbidden to close the output breaker OUTPUT 2 3 6 Switch to Inverter Output from Maintenance Bypass Before perform the operation of switching to inverter power supply from...

Страница 69: ...dicators on and the buzzer long beeps After pressing the EPO button the UPS is with no output the power supply for load is interrupted When the system stay in maintenance bypass status after pressing...

Страница 70: ...If all UPS monitor page without abnormal alarm close battery breaker of each UPS s battery cabinet if there are many groups battery it is necessary to close each battery breaker and then close the tot...

Страница 71: ...with the output breaker front end phase A of UPS2 the other pen connect with the output breaker back end phase A of UPS2 measure the voltage different between front end and back end of UPS2 output bre...

Страница 72: ...at any time Close the load of parallelsystem keep the UPS run without load for 5min to eliminate inner heat Perform UPS Shutdown to close all UPS system turns to bypass power supply Disconnect the lo...

Страница 73: ...User Manual 2 Overview 65 EPO linkage is not enabled Press EPO button of one UPS the output of this UPS will be closed Press the EPO button of total system all paralleled UPS will be shut down and all...

Страница 74: ...if the voltage of multi meter is normal and the polarity is reverse connected If the result is abnormal it is strictly forbidden to close the battery breaker Do not wear any conductive metal objects d...

Страница 75: ...during using Fully charge the battery immediately after discharge 24h at latest and then the battery can discharge again It is strictly forbidden to discharge the not fully charged battery or it will...

Страница 76: ...wires are wrongly connected such as neutral wire and ground wire or live wire and grounding case is wrongly connected or the three phase output wire is wrongly connected 3 After startup the UPS outpu...

Страница 77: ...tartup and work a period of time buzzer long beeps and the touch screen shows battery low voltage The mains voltage is too low and the UPS works in battery inverting status finally the battery is unde...

Страница 78: ...n if necessary close the user load and disconnect the input and output breaker of the UPS to avoid further damage for the UPS Inform the engineering technicist to maintain How to deal with the fault o...

Страница 79: ...way transportation do not put the device in the open air The device cannot suffer any rain snow or liquid material or mechanical damage Storage When storing the device place the device according to th...

Страница 80: ...r to use Vin 80Vac 175Vac Linear decrease rated power to use Input frequency range Hz 40 70 Bypass synchronization tracking range Hz 50 60 6 Bypass input voltage 220 230 240 phase voltage Input power...

Страница 81: ...n 105 rated load it runs normally When the load in the range of 105 115 rated load it will turns to bypass 60min later When the load in the range of 116 130 rated load it will turns to bypass 10min la...

Страница 82: ...and inner temperature parameter setting history record etc LED display Work status and fault indication of UPS Alarm function Alarm for input abnormal batterylow voltage overload fault etc Communicat...

Страница 83: ...IST7 10 30 kVA User Manual A Technical Specifications 75 Model Index 10kVA 20kVA 30kVA Size W D H mm 320 840 867 4 5 0 8 4 0 9 6 7 Weight kg 120 1 6 0 Specifications are subject to change without prio...

Страница 84: ...ser Manual 76 B Acronyms and Abbreviations A AC Alternating Current D DC Direct Current DSP Digital Signal Processor E ECO Energy Control Operation EPO Emergency Power Off L LED Light emitting Diode P...

Страница 85: ...AEC UPS IST7 10 30 kVA User Manual B Acronyms and Abbreviations 77 S SNMP Simple Network Management Protocol T THDv Total Harmonic Distortion of output voltage U UPS Uninterruptible Power Supply...

Страница 86: ......

Отзывы: