2 Overview
UPS IST3-J (1-3kVA)
User Manual
22
more than 1s to quit the set page, the setting is successful. In the RCK mode, the LCD display is as
shown Figure2-30.
Figure2-30
RCK mode
TWR mode
When LCD displays RCK mode and it has to set to TWR mode, in the set page, three characters
"TWR" flicker. If you confirm the selection, press and hold " " button more than 1s to quit the set
page, the setting is successful. In the TWR mode, the LCD display is as shown Figure2-31.
Figure2-31
TWR mode
Charging current (optional)
If the UPS is equipped with a charging module, the charging current can be set that is
1A/2A/3A/4A/5A/6A/7A/8A (the default setting is 1A). If you want to modify the charging current,
select the charging current (the recommended current is 0.1C~0.2C) based on the UPS battery
amperage configuration C. If you confirm the selection, press and hold " " button more than 1s to
quit the set page, the setting is successful. The LCD display is as shown Figure2-32.