AEC ILLUMINAZIONE Kaos 1 Скачать руководство пользователя страница 2

 

 

MOUNTING AND MAINTENANCE 

INSTRUCTION 

KAOS_IM_ENG  - Rev.09 of 03/05/16 

Page 2 of 2 

Made in Italy 

 
 
 

In order to insure double insulation 
characteristic of the feeder cable, we 
would advise that you first secure the 
feeder cable to the internal cable 
clamp, remove approximately 25mm 
of external sheathing, and 6mm of 
sheathing from the internal wires.

 

<   2 5 mm 

6

7 mm 

ELECTRICAL LINE CONNECTION 

ATTENTION 

 

a) 

The luminaire can be installed close to flammable surfaces. 

b) 

Class II luminaires must be installed in such a way that it is impossible for any exposed metal part to come in contact with electrical 
components. 

c) 

Luminaires for Metal Halide lamps must be always complete with its protective screen. 

d) 

For luminaires with Metal Halide lamps, damaged protective shields can onl

y be replaced with original AEC Illuminazione’s replacement 

shields. 

e) 

On luminaires for Metal Halide lamps use only UV Stop protected lamps. 

f) 

This luminaire has been designed and manufactured following all relevant standards. The installation must be done by experienced personnel 
and following the instructions. 

The present instruction paper has to be kept for any future maintenance operation on the luminaire. 
Non compliance with the above will automatically release AEC Illuminazione Srl from any responsibility.

 

 

Lamp type 

– Weight 

Model 

Lamp type 

Weight  [gr] 

 

 

 

 

 

Plastic cover 

 Aluminium cover 

MBF 

SHP E 

SHP T 

MHL E 

MHL T 

Empty 

Wired 

Empty 

Wired 

 

 

 

 

 

 

 

 

 

 

   

 

80 W 

70 W 

70 W 

70 W 

70 W 

 

6.500 

 

8.000 

125 W 

100 W 

100 W 

100 W 

100 W 

5.500 

7.000 

7.000 

8.500 

150 W 

150 W 

150 W 

150 W 

 

7.500 

 

9.000 

 

 

 

 

 

 

 

 

 

 

 

 

250 W 

150 W 

150 W 

150 W 

6.500 

8.500 

8.000 

10.000 

250 W 

250 W 

250 W 

250 W 

9.500 

11.000 

400 W 

400 W 

11.000 

12.500 

 

Shape coefficient: 1,2 

Wind catching area 

0,10 m

2

 

0,12 m

2

 

0,20 m

2

 

0,24 m

2

 

Dimensions 

Dimensions 

Bracket Ø 60mm 15° 

Bracket Ø 60mm 10° 

Bracket Ø 60mm 5° 

Bracket Ø 60mm 0° 

Bracket Ø 42mm 15° 

Bracket Ø 42mm 10° 

Bracket Ø 42mm 5° 

Bracket Ø 42mm 0° 

Pole head Ø 76mm 

Pole head Ø 60mm

 

NO Accessory (bracket 15°) 

Accessory 10° (bracket 10°) 

Accessory -5° (bracket 5°) 

Accessory 0° (bracket 0°) 

Mo

unt

ing

 

Suggested height of installation 

Power [W] 

H min [m] 

H max [m] 

70 

150 

10 

400 

12 

Max height of installation: 15m

 

WIRING SCHEME 

70 W 

SHP                 70 W ÷ 400 W SHP 

80 W ÷ 250 W  MBF                 70 W ÷ 400 W MHL

 

A

 

– Ballast

 

L

 

– Lamp

 

f

 

–  Fuse (500V)

 

C

 

– Capacitor

 

Z

 

– Ignitor

 

 

 

DON’T 

USE 

THIS 

POSITION 

 

ATTENTION

:  use  only  the 

allowed positions (0° ,-5°,-10°). 
 

Functioning position 

Suggested: 

α

 = 90° 

α

 

Отзывы: