Surge
Meet IEEE 587 standard
Operation
Elevation: 6,000m max, Humidity: 0%-95%(without
condensation formation), Temperature: 0-40 deg C
Audible noise
<40dBA (1 meter from
surface)
<45dBA (1 meter from surface)
ENVIRONME
NT
Storage condition 15000
meters
max.
elevation
A
PPENDIX B
.2
S
PECIFICATION
MODEL 2500VA
3000VA
1000AL
2000AL
3000AL
Capacity
2500VA 3000VA 1000VA 2000VA 3000VA
Voltage
100V, 110V, 120V, 220V, 230V, 240V, +/-25%,Single phase
INPUT
Frequency
50 or 60Hz +/-5% (auto sensing)
Voltage (on
battery)
Pure sine wave output at n/-5%
Frequency (on
battery)
50 or 60Hz +/-0.5%
OUTPUT
Voltage
Regulation
AVR
AVR automatically increase output voltage 15% above input
voltage if -9% to-25% of nominal. AVR decrease output voltage
15% below input voltage if+9% to +25% of nominal
Spike
Protection
320 Joules, 2ms
Unit Input
Breaker for overload & short circuit protection
EMI/RFI filter
10dB at 0.15MHz, 50dB at 30MHz
Overload
Protection
UPS automatic shutdown if overload exceeds 110% of nominal
at 20 second and 125% at 2 seconds.
Transfer Time
2~4 milliseconds, including detection time
PROTECTION
AND
FILTERING
Short Circuit
UPS output cut off immediately or input fuse protection
Type
Hot swappable, Sealed, Maintenance-free lead acid
Typical Battery
Life
3 to 6 years, depending on number of discharge cycles and
ambient temperature
Typical
Recharge Time
4 hours (to 90% of full capacity)
Nominal Battery
Voltage
48V 48V 24V 48V 48V
Charge
Current
2A 2A 4A 4A 4A
BATTERY
Supplied
Battery Packs
Built-in
External
Pack
Upon
request
Upon
request
Upon
request