29
WISE-4000 User Manual
Chapter 2
P
roduct
Specifications
2.7.4
Block Diagram
Figure 2.26 WISE-4050 Block Diagram
2.8
WISE-4051
2.8.1
I/O Specification
Digital Input
–
Channel: 8
–
Logic level
–
Dry Contact 0: Open
1: Close to DI COM
–
Wet Contact 0: 0~3 V
DC
or -3~0 V
DC
1: 10~30 V
DC
or -30~-10 V
DC
(3 mA min.)
–
Channel 0~3 should be configured to dry contact or wet contact in the same
time
–
Channel 4~7 should be configured to dry contact or wet contact in the same
time
–
Isolation: 3,000 V
rms
–
Supports 32-bit Counter Input Function (Maximum signal frequency 3 kHz)
–
Keep/Discard Counter Value when Power-off
–
Supports Frequency Input Function (Maximum frequency 3 kHz)
–
Supports Inverted DI Status
RS-485 Port
–
Number of Ports: 1
–
Port Connector: 3.5mm spacing plug-in screw terminal block (shared with I/O
and power)
–
Baud Rate (bps): 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
–
Data Bits:7, 8
–
Stop Bits: 1, 2
–
Parity: None, Odd, Even
–
Flow Control: Auto flow control
–
Signals: DATA+ and DATA-
–
Protection: 15 kV ESD
–
Supported Protocol:
–
Modbus/RTU (Total 32 address by max. 8 instructions)
Содержание WISE-4000 Series
Страница 1: ...User Manual WISE 4000 Series IoT Ethernet I O Module ...
Страница 9: ...Chapter 1 1 Product Overview ...
Страница 17: ...Chapter 2 2 Product Specifications ...
Страница 42: ...WISE 4000 User Manual 34 2 9 4 Block Diagram Figure 2 35 WISE 4060 Block Diagram ...
Страница 43: ...Chapter 3 3 Hardware Installation ...
Страница 48: ...WISE 4000 User Manual 40 3 2 3 Stack Mounting Figure 3 8 Stack Mounting Figure 3 9 Finished Stack Mounting ...
Страница 51: ...Chapter 4 4 System Configuration ...
Страница 100: ...WISE 4000 User Manual 92 ...
Страница 101: ...Appendix A A I O Modbus Mapping Table ...
Страница 124: ...WISE 4000 User Manual 116 ...
Страница 125: ...Appendix B B REST for WISE 4000 Series ...