background image

WISE-221X User Manual

iv

Warnings, Cautions and Notes

Document Feedback

To assist us in making improvements to this manual, we would welcome comments
and  constructive  criticism.  Please  send  all  such  -  in  writing  to:  support@advan-
tech.com

Package List

Before setting up the system, check that the items listed below are included and in
good condition. If any item does not accord with the table, please contact your dealer
immediately.

WISE-2210-NA

1 x WISE-2210 module

1 x Mounting bracket

1 x Quick start manual
*Antenna should be ordered respectively per required frequency range.

WISE-2211-NA

1 x WISE-2211 module

1 x Mounting bracket

1 x Quick start manual
*Antenna should be ordered respectively per required frequency range.

Warning!

Warnings indicate conditions, which if not observed, can cause personal 
injury!

Caution!

Cautions are included to help you avoid damaging hardware or losing 
data. e.g.There is a danger of a new battery exploding if it is incorrectly 
installed. Do not attempt to recharge, force open, or heat the battery. 
Replace the battery only with the same or equivalent type recom-
mended by the manufacturer. Discard used batteries according to the 
manufacturer's instructions.

Note!

Notes provide optional additional information.

Note!

User have to install a antenna when they use WISE-2210 or WISE-
2211.

Содержание WISE-221 Series

Страница 1: ...User Manual WISE 221X IoT Wireless Sensor Node ...

Страница 2: ...on Advantech assumes no liability under the terms of this warranty as a consequence of such events Because of Advantech s high quality control standards and rigorous testing most of our customers never need to use our repair service If an Advantech product is defec tive it will be repaired or replaced at no charge during the warranty period For out of warranty repairs you will be billed according ...

Страница 3: ...led and used in accordance with the instruction manual may cause harmful interference to radio communications Opera tion of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense This transmitter must not be co located or operating in conjunction with any other antenna or transmitter Techni...

Страница 4: ...ired frequency range WISE 2211 NA 1 x WISE 2211 module 1 x Mounting bracket 1 x Quick start manual Antenna should be ordered respectively per required frequency range Warning Warnings indicate conditions which if not observed can cause personal injury Caution Cautions are included to help you avoid damaging hardware or losing data e g There is a danger of a new battery exploding if it is incorrect...

Страница 5: ...s may cause fire or electrical shock 13 Never open the equipment For safety reasons the equipment should be opened only by qualified service personnel 14 If one of the following situations arises get the equipment checked by service personnel The power cord or plug is damaged Liquid has penetrated into the equipment The equipment has been exposed to moisture The equipment does not work well or you...

Страница 6: ...WISE 221X User Manual vi DISCLAIMER This set of instructions is given according to IEC 704 1 Advantech disclaims all responsibility for the accuracy of any statements contained herein ...

Страница 7: ...the PC is on Disconnect power before making any configuration changes The sudden rush of power as you connect a jumper or install a card may damage sensitive elec tronic components NCC 警语 第十二條 經型式認證合格之低功率射頻電機 非經許可 公司 商號或使用者均不得 擅自變更頻率 加大功率或變更原設計之特性及功能 第十四條 低功率射頻電機之使用不得影響飛航安全及干擾合法通信 經發現有干擾 現象時 應立即停用 並改善至無干擾時方得繼續使用 前項合法通信 指依電信法 規定作業之無線電通信 低功率射頻電機須忍受合法通信或工業 科學及醫療用電波 輻射性電機設備之干擾 Frequency Type Gain Bran...

Страница 8: ...WISE 221X User Manual viii ...

Страница 9: ...onfiguration Interface 9 2 8 Pin Assignment 10 Figure 2 3 WISE 221X Pin Assignment 10 2 9 Application Wiring 10 Figure 2 4 WISE 2210 I O Pinout Application Wiring 10 Figure 2 5 WISE 2211 I O Pinout Application Wiring 11 2 10 Block Diagram 11 Figure 2 6 WISE 2210 2211 Block Diagram 11 2 11 Accessory CT Current Transformer 11 Chapter 3 Mechanical and Hardware Installation 13 3 1 Interface Introducti...

Страница 10: ...lt Settings 21 4 2 3 Module Authorization 22 4 3 Install WISE Studio and Configure End Devices 23 4 4 Connection between AP and Nodes 24 4 5 Configure WISE 4210 AP 25 4 6 Setup WISE 221x Network 27 4 7 WISE 221x IO configuration 27 4 7 1 Date Update 27 4 7 2 I O Status 28 4 8 Access WISE 221x Data by Modbus TCP Protocol 29 4 9 Push WISE 4210 data by RESTful Web Service 31 4 10 Access WISE 4210 I O...

Страница 11: ...Chapter 1 1 Product Overview ...

Страница 12: ...3 System Architecture You can use WISE 2210 and CT Current Transformer to measure the current of facility equipment industrial machines and other production equipment You can also use WISE 2211 to acquire sensor data from analog inputs connected to the 4 20mA sensor transmitter WISE 221x transmits sensor data to WISE 4210 AP via Advantech LPWAN wireless technology WISE 4210 AP provides Ethernet an...

Страница 13: ...User Manual Chapter 1 Product Overview Figure 1 1 System Architecture 1 4 Mechanical Design and Dimensions Figure 1 2 WISE 221X Dimension Front and Side Note User need to install antenna when you use WISE 2210 2211 ...

Страница 14: ...USB and COM 1 6 Reset button Figure 1 4 Reset button LED Color Behavior Description COM RF Tx Green On Flash when data transmission Transmit data to AP Always on In bootloader mode off Idle USB Green On USB connector plug in off USB connector plug out ...

Страница 15: ...Chapter 2 2 Product Specification ...

Страница 16: ...ps Topology Star Network Capacity Up to 64 end nodes WISE 221X Channel list EU868 868MHz 865 2 868 8 BW 400KHz Figure 2 1 channel list for EU868 NA923 923MHz 920 8 924 4 BW 400KHz Figure 2 2 channel list for NA923 Channel Freq MHz Channel Freq MHz Channel Freq MHz Channel Freq MHz 1 865 2 4 866 4 7 867 6 10 868 8 2 865 6 5 866 8 8 868 0 3 866 0 6 867 2 9 868 4 Channel Freq MHz Channel Freq MHz Cha...

Страница 17: ...00 mA current transformer In other words WISE 2210 measures data and gets power current from a connected current transformer 2 Charging time Test Condition Data Rate 50Kbps Transmit Power 5dBm Frequency 920 8MHz Distance 500 meters line of sight Note Equipment will operate below 30 humidity However static electricity problems occur much more frequently at lower humidity levels Make sure you take a...

Страница 18: ...tility WISE Studio WISE 4210 AP Protocols TCP IP UDP HTTP HTTPS DHCP ARP SNTP MQTT Modbus TCP Modbus RTU WISE 4210 AP supports RESTful Web API JSON for mat 2 5 Configuration Interface WISE 221X Interface USB virtual COM port Connector Micro B USB USB chipset Silicon Labs CP210x Driver CP210x USB to UART Bridge VCP Drivers https www silabs com products development tools software usb to uart bridge ...

Страница 19: ...dity However envi ronments with low relative humidity are prone to problems with electro static discharge Therefore you should ensure that you take adequate precautions by using ground straps anti static floor coverings or similar equipment whenever you handle this equipment especially in low humidity environments Note To order an Advantech CT Current Transformer refer to section 2 11 Accessory CT...

Страница 20: ... Assignment Figure 2 3 WISE 221X Pin Assignment 2 9 Application Wiring WISE 2210 Analog input current Alternating Current 0 100 mA Figure 2 4 WISE 2210 I O Pinout Application Wiring WISE 2211 Analog input current Direct Current 4 20mA ...

Страница 21: ...rimary Accuracy Operating Temperature 96PD CT241 60A 3 60A 10 0 0 2mm Class 0 5 20 65 C 96PD CT248 100A 5 100A 15 7 0 3mm Class 0 5 40 65 C 96PD CT24F 200A 10 200A 20 5 0 3mm Class 0 5 40 85 C 96PD CT24C 300A 15 300A 35 7 0 3mm Class 0 5 40 85 C Note The class designation is an approximate measure of the CT s accuracy The ratio primary to secondary current error of a Class 1 CT is 1 at rated curre...

Страница 22: ...WISE 221X User Manual 12 ...

Страница 23: ...Chapter 3 3 Mechanical and Hardware Installation ...

Страница 24: ...WISE 221X User Manual 14 3 1 Interface Introduction Figure 3 1 WISE 221x Interface Introduction ...

Страница 25: ... Mounting Applicable installation methods are briefly described in the following sections 3 2 1 Poll Mount Use a screwdriver to fasten WISE 221X and mounting kit Then use a cable tie to fasten the mount kit and pole Figure 3 2 Pole Mounting front Figure 3 3 Pole Mounting back ...

Страница 26: ... can be fixed to a wall with a mounting kit Use a screwdriver to fasten the mounting adapter to your module and use the end brackets included in the package in order to keep it from sliding Figure 3 4 Wall Mounting Install Figure 3 5 Wall Mounting Install ...

Страница 27: ...mounting rails Use a screwdriver to fasten the DIN rail adapter to your module and use the end brackets included in the pack age in order to keep it from sliding Figure 3 6 DIN Mounting Install Figure 3 7 DIN Mounting Install Front Note DIN Rail Mounting adapter for WISE 221X is available for ordered 1970000000T000 DIN Rail Mounting kit ...

Страница 28: ...WISE 221X User Manual 18 Figure 3 8 DIN Mounting Install Back 3 3 Power Supply Wiring WISE 221X is a self powered sensor node power source is obtained from the analog input channels ...

Страница 29: ...Chapter 4 4 System Configuration ...

Страница 30: ...ART Bridge VCP Drivers https www silabs com products development tools software usb to uart bridge vcp drivers 2 Connect WISE 4210 AP to your computer via the RJ 45 LAN port and config ure the IP address of your computer as the default IP address of mod ule 10 0 0 1 Figure 4 1 Connection WISE 221X and WISE 4210 AP Note Micro B USB cable for configuring WISE 4210 nodes is available for ordered 1700...

Страница 31: ...le Android 4 0 Ice Cream Sandwich Chrome in Google Android 4 0 Ice Cream Sandwich For PC platforms the minimum requirements of web browsers are as below Internet Explorer version 11 Google Chrome version 30 Mozilla Firefox version 25 4 2 2 Factory Default Settings IP Mode Static IP Address Default IP 10 0 0 1 Subnet Mask 255 0 0 0 Default Gateway 0 0 0 0 IP Mode Static HTTP Port 80 Mobile Browser ...

Страница 32: ...ons Account root admin user Device information View View View Device setting Edit Edit Deny System Restart Edit Edit Edit Module Locate Edit Edit Edit Change passwords Edit Deny Deny Reset Password Edit Deny Deny Reset to default Edit Deny Deny Access control configurations Edit Edit Deny Group configurations Edit Edit Deny Download upload processes Edit Edit Deny Network configurations Edit Edit ...

Страница 33: ... Studio Step 3 Power up WISE 4210 AP Step 4 Use a USB cable to communicate WISE 221x through a computer Step 5 Click Go to Configuration while it shows available USB Serial in USB Serial box If device cannot be connected through USB please install CP210x USB to UART Bridge VCP Drivers from the following website https www silabs com products development tools software usb to uart bridge vcp drivers...

Страница 34: ...nk only no downlink Data Rate bps Lower data rate is helpful of extending communication range while higher data rate can reduce the communication time which allows more data to be uploaded to AP in the same period of time Tx Power dBm Lower Tx power helps to reduce the power consumption higher Tx power enhances the communication distance Baseband kHz If several WISE 4210 AP or sub GHz networks are...

Страница 35: ... lowing figure the IP address of this computer is configured as 10 0 0 100 Find the Ethernet box in WISE Studio and click Go to Configuration Step 3 After the above steps WISE Studio will search WISE 42xx series under the same subnet and you will find the IP address of WISE 4210 AP in Device Informa tion Step 4 Enter the IP address of WISE 4210 AP in the browser or you can keep using WISE Studio t...

Страница 36: ...ink only no downlink Data Rate bps Lower data rate is helpful for extending communication range while higher data rates can reduce the communication time which allows more data to be uploaded to AP in the same period of time Baseband kHz If several WISE 4210 AP or sub GHz networks are in the same area users can select different basebands to reduce the interference of each network Please note that ...

Страница 37: ...SI dBm Signal strength when data updated from end device to AP RSSI will be updated after WISE 4210 AP received data from WISE 221x end node devices An RSSI level higher than 100dBm is recommended Inactive Time Elapsed time since last time WISE 4210 AP receives data from an end node devices If an end node device update data every 5 second and it has good wireless signal quality Inactive Time will ...

Страница 38: ...s the power current of the facility equipment and machines See figure 1 1 CT Secondary Current Value mA The output power current of the CT In other words CT Secondary Current Value is the power current WISE 2210 is using Note Users can order Advantech accessory CT Current Transformer please see chapter 2 11 Accessory CT Current Transformer If the user wants to choose a CT themselves please make su...

Страница 39: ...Protocol Go to Configuration Modbus Modbus ID to check and configure the Modbus ID of each MAC address of AP and end node devices User can use Modbus TCP and Modbus RTU protocol to access each end devices from WISE 4210 AP polling data from different Modbus ID for different end node devices or AP ...

Страница 40: ...38 3 Read 40139 40140 4 Read 40141 40142 5 Read 40143 40144 6 Read 40145 40146 7 Read 40147 40148 Average Ch 0 7 Read 40201 0 Type Code The type codes of channels for average value can t be changed Read 40202 1 Read 40203 2 Read 40204 3 Read 40205 4 Read 40206 5 Read 40207 6 Read 40208 7 Read 40209 Average Ch 0 7 Read 40231 40232 0 Physical AI Floating Value IEEE754 Read 40233 40234 1 Read 40235 4...

Страница 41: ...al Chapter 4 System Configuration 4 9 Push WISE 4210 data by RESTful Web Service Step 1 Configure the Private Server in Configuration Cloud Step 2 Enable the Data Logger function in Advanced Data Logger Logger Configuration ...

Страница 42: ... Request GET lpwan_message slot_macID Example Request GET lpwan_message slot_AD4210112233 for WISE 4210 module Content type application json Response 200 OK TIM 2014 11 11T15 48 32 08 00 UID WISE 4210 AP_00D0C90E8738 MAC 00 D0 C9 FE 16 01 Rssi 33 Record 0 0 1 0 0 0 2 50 0 0 3 10 0 1 4 0 0 1 5 456 0 1 6 0 0 0 30 0 0 0 31 16 0 0 32 32767 JSON array name definition Field Abbreviation Data Type Array ...

Страница 43: ...O 8601 Ex 1994 11 05T08 15 30 05 00 corresponds to November 5 1994 8 15 30 am US Eastern Standard Time UUID UID String R Universally Unique Identifier UUID Max 32 characters MAC ID MAC String R MAC address ex 00 D0 C9 F0 63 F7 RSSI Rssi Number R The RSSI value Recording message Record Array R The data type in array is as follows Number Number Number Number The information in array is as follows Sl...

Страница 44: ...9 Historical Minimum AI value 10 AI value after scaling 11 AI status flags 12 AI engineering value 13 Historical Maximum AI engineering value 14 Historical Minimum AI engineering value 24 DI period counter mode 25 DI low to high trigger tick 30 Expansion bit data 31 Expansion bit error code 32 Expansion word data 33 Expansion word error code 40 Sensor engineering value 41 Sensor maximum engineerin...

Страница 45: ...35 WISE 221X User Manual Chapter 4 System Configuration ...

Страница 46: ...ations are subject to change without notice No part of this publication may be reproduced in any form or by any means electronic photocopying recording or otherwise without prior written permis sion of the publisher All brand and product names are trademarks or registered trademarks of their respective companies Advantech Co Ltd 2019 ...

Отзывы: