Power Connection
EKI-2528I-M12 switch supports 12 ~ 48 VDC power
input using 4-pin male M12 A-code connector.
STEP 1:
Insert a corresponding power cord on the power
connector to connect EKI-2528I-M12.
STEP 2:
Screw the nut on the power cord connector to
ensure a tight connection between power cord and
EKI-2528I-M12.
The switches must be powered by using UL61010 or
UL61010-2-201 listed power source, rated 12-48Vdc,
1.5 minimum and Tma 75 degree C.
Suggestion: Suitable for field wiring. Female Connector, 4
wire, Plug straight M12, A-coded, Push-in connection,
tighten torque 1.5 Nm, UL 2238 Listed cable (UL CYJV
Listed)
Startup Manual 2
Mounting
DIN-rail Mounting
STEP 1:
Install the DIN-Rail Mounting Kit.
DIN-Rail Screw Size: M3x6L
STEP 2:
Install the Switch.
STEP 3:
Remove the Switch.
Wall Mounting
STEP 1:
Prepare the 4 screw holes on the wall according to the
switch. Screw hole size: 5.0mm
STEP 2:
Screw in the 4 screws through the screw holes on the
switch to the wall.