Before you begin, be  

sure you have 

the following:

Model BB-485DRCI-PH

3-Way Isolated RS-232 to

RS-422/485 Converter

+ BB-485DRCI-PH Converter

+ 10 to 48 Vdc Power Supply

QUICK START

GUIDE

Connecting a Signal Ground 

(common, reference) on the RS-422/485 side.

 

The specifications for most RS-422 and RS-485 

devices indicate that the device can withstand a 

maximum VCM of -7 Volts to +12 Volts. The function of 

the GND connection is to tie the signal grounds of all 

nodes on a network to one common ground potential. 

This ensures that the common mode voltage cannot 

exceed the specified value.

A signal ground is required on Model BB-485DRCI-

PH because it is an optically isolated device. If you do 

not have a signal ground (common, reference) on your 

RS-422/485 device, you can connect to the DC power 

ground of your RS422/485 device.

Caution: Make sure that this is connected correctly.

Note: Do Not use the shield drain wire as the signal 

ground between RS-422/485 devices.

SUITABLE FOR USE IN CLASS I, DIVISION 2, GROUPS 

A, B, C AND D HAZARDOUS LOCATIONS, OR 

NONHAZARDOUS LOCATIONS ONLY.

CONVENANT À L’EMPLOI DANS LES SITES DANGEREUX 

DE CLASSE I, DIVISION 2, GROUPES A, B, C ET D, OU 

DANS LES SITES NON HASARDEUX SEULEMENT.

WARNING - EXPLOSION HAZARD - SUBSTITUTION OF 

ANY COMPONENT MAY IMPAIR SUITABILITY FOR CLASS 

I, DIVISION 2.

ATTENTION - DANGER D’EXPLOSION - LA 

SUBSTITUTION DE COMPOSANTS PEUT ENTRAÎNER 

UNE ADÉQUATION À LA CLASSE I, DIVISION 2.

WARNING - EXPLOSION HAZARD - DO NOT 

DISCONNECT EQUIPMENT WHILE THE CIRCUIT IS 

LIVE OR UNLESS THE AREA IS KNOW TO BE FREE OF 

IGNITABLE CONCENTRATIONS.

ATTENTION - DANGER D’EXPLOSION - LA SUBSTITUTION DE 

COMPOSANTS PEUT ENTRAÎNER UNE ADÉQUATION À LA 

CLASSE I, DIVISION 2.

Field wiring connections must be made using 105 °C minimum 

copper supply wires.

Les connexions de câblage sur site doivent être réalisées en 

utilisant des câbles d’alimentation en cuivre de 105 °C minimum.

To be installed in accordance with control drawing 8512r001.

Pour être installé conformément au dessin de contrôle 8512r001.

UL Class 1/Div. 2 Information

7

Troubleshooting

6