5
Calibration voltage (ADAM-5017/5018)
Module
Input Range Code
(Hex)
Input Range
Span Calibration
Voltage
00h
±15 mV
+15 mV
01h
±50 mV
+50 mV
02h
±100 mV
+100 mV
03h
±500 mV
+500 mV
04h
±1 mV
+1 V
05h
±2.5 V
+2.5 V
06h
±20 mV
+20 mA (1)
0Eh
J thermocouple 0 to
1370°C
+50 mV
0Fh
K thermocouple 0 to
1370°C
+50 mV
10h
T thermocouple -100 to
400°C
+22 mV
11h
E thermocouple 0 to
1000°C
+80 mV
12h
R thermocouple 500 to
1750°C
+22 mV
13h
S thermocouple 500 to
1800°C
+22 mV
5018
14h
B thermocouple 500 to
1800°C
+152 mV
07h
Not used
08h
ºC
±10 V
+10 V
09h
±5 V
+5 V
0Ah
±1 V
+1 V
0Bh
±500 mV
+500 mV
0Ch
±150 mV
+150 mV
5017
0Dh
±20 mA
+20 mV (1)
Table 6-1: Calibration voltage of ADAM-5017/5018