Ring Operation

Several ADAM-4542+ modules can be cascaded to form a ring connection. With a circumstance that users plan to 

use a HMI/SCADA to connect multiple kinds of IO device with ADAM-4542+, users can apply ring architecture 

to save lots of cost caused from the number of modules and the length of optical fiber. Following diagrams 

demonstrates the Ring application. Ring Operation mode is set by DIP4 of SW3.

Limitation

While applying ring operation, please notice the following limitations.

 

ƒ

It only supports the half duplex.

 

ƒ

 Up to 100 ADAM-4542+ can be connected over a distance of 1,500 km.

 

ƒ

Under ring operation, RS-232/422/485 all need to set SW2 for baud rate.

Normal Operation

Содержание ADAM-4542+

Страница 1: ...42 for a redundant architecture This special design offers higher reliability Features Direct plug and play Easily mounted on a DIN rail panel or piggybacked Transmission speeds of up to 921 6 kbps RS422 485 Optical fibers enable transmission of up to 15 km Half Full duplex bidirectional transmission mode Support for ring mode Avoid lightning strikes and EMI RFI Prevents damage from electrostatic ...

Страница 2: ...hen you need to set SW2 Baud Rate SW2 1 2 3 4 5 6 7 8 9 1200 bps ON OFF OFF OFF OFF OFF OFF OFF OFF 2400 bps OFF ON OFF OFF OFF OFF OFF OFF OFF 4800 bps OFF OFF ON OFF OFF OFF OFF OFF OFF 9600 bps OFF OFF OFF ON OFF OFF OFF OFF OFF 19 2 kbps OFF OFF OFF OFF ON OFF OFF OFF OFF 38 4 kbps OFF OFF OFF OFF OFF ON OFF OFF OFF 57 6 kbps OFF OFF OFF OFF OFF OFF ON OFF OFF 115 2 kbps OFF OFF OFF OFF OFF OF...

Страница 3: ...o save lots of cost caused from the number of modules and the length of optical fiber Following diagrams demonstrates the Ring application Ring Operation mode is set by DIP4 of SW3 Limitation While applying ring operation please notice the following limitations It only supports the half duplex Up to 100 ADAM 4542 can be connected over a distance of 1 500 km Under ring operation RS 232 422 485 all ...

Страница 4: ...f module there are two sets of LED which are status LED and TX RX LED The meaning for LED display method is described as following table Description Status TX RX Green Red Red TransmittingData ON Receiving Data ON Power Fiber state Fiber Rx Redundant Working ON Power Fiber state Fiber Rx Redundant Failed ON If the module is set as a secondary module in the redundant structure no LED will be ON ...

Страница 5: ...artup Manual 5 Wiring Diagrams Non Redundant System Redundant System Redundant systems can also support RS 422 In a redundant system the ground of the external power for modules must be connected together ...

Страница 6: ... Reduce attenuation by reducing connector loss transmission distances etc The connection between the communication ports is neither DTE to DTE nor DCE to DCE connection Add a converter to one of the optical modems so that the pin assignments from the communication port to the modem are from pin 2 to pin3 and from pin 3 to pin 2 Damage Test If none of the above resolved your problem your module may...

Отзывы: