background image

 ENTER 

PASSWORD XXXX

 

ENTER  To change password

 

ENTER  Use numeric keys to set password

 

  

then press ENTER to accept.

  

RESET METER

 

ENTER  Count  zeroed

 

Dry Contact Head

 

ENTER  To change to HALL EFFECT

 

English Units

 

ENTER  Metric Units

 

GAL/PULSE

 

ENTER  To change value

 

ENTER  Use numeric keys to change gal/pulse

 

 

then press ENTER to accept.

 

 

BLEED/PULSE

 

ENTER    To change value.

 

 

Use numeric keys to change gal/pulse 

 

ENTER  for bleed then press ENTER to

 

 

accept.

 

PUMP LOW DRUMS

 

ENTER   To change LOW DRUM NO PUMP

 

BAUD RATE 200

 

ENTER  To change baud rate

4. 

SYSTEM SET MENU

This  menu  is  used  to  configure  the  controller  to 

specific  operational  needs.    Some  of  the  items  in 

this menu may not apply depending on the controller 

model but will always be present.

PASSWORD 

-

 

If  a  value  of  0000  is  entered, 

a  password  is  not  required.    If  a  password  is 

entered, it must be used to operate the controller. 

If the first digit is 0, relays may be activated without 

a password.

RESET WATER METER COUNT

 

-

 

Does not apply 

unless the  unit has selectable feed timer.

WATER METER IN 

- Select a contacting head 

water meter or a paddle wheel flow meter.

GAL/PULSE 

-

 

If a feed timer is using a contacting 

head water meter this tracks make-up volume by 

entering the number of gallons a contact equals. 

Use • key to change to pulse/gal for flowmeter.

LOW DRUM NO PUMP/PUMP LOW DRUMS

 

-

 

If 

unit has low level alarms, allows the associated 

feed timer to be forced off when drum is low.

BAUD RATE 

- For units ordered with the serial 

line or modem option.

--SYSTEM SET--

System Set continued on next page.

Содержание MicroTron

Страница 1: ... Installation Maintenance Repair Manual Advantage Controls P O Box 1472 Muskogee OK 74402 Phone 800 743 7431 Fax 888 686 6212 www advantagecontrols com HE 22 1 08 MicroTron Timer Controller Manual ...

Страница 2: ...nel Description 6 V System Operation Overview 7 A Description of Set Up Menu Screens 7 1 Chem Feed Set 8 2 Biocide Set 9 3 Clock Set 10 4 System Set Menu 11 5 Diagnostics Menu 13 B Run Menu 14 VI Troubleshooting 14 VII Warranty 30 Day Billing Memo Policy 15 Instructions herein apply to all Microtron chemical feed or biocide timers or combinations of the two Additional options described in this man...

Страница 3: ...ate the timer to run from 0 99 minutes 59 seconds in minutes and seconds 2 Percentage The relay is on for a percentage of a continuously repeating cycle time Both the percentage and cycle time are programmable 28 Day Feed Timers 28 day feed timers typically used for biocide feed are based on a 28 day cycle with two independent programmable feed cycles allowing for feed on selectable days and weeks...

Страница 4: ...al codes 2 Power line voltage must be disconnected while making any connections If power is supplied to the unit line voltage will be present on the relay cards 3 Low voltage signal wires probes flow switch water meter etc should never be run in conduit with high voltage wires Conduit Connections for LCD Units Relay Power Board Logic Board Serial Line Connection R B R B R B R B Level 1 Level 2 Lev...

Страница 5: ...cations that expose the controller to direct sunlight vapors vibration liquid spills or extreme temperatures less than 0 F 17 8 C or greater than 120 F 50 C EMI electromagnetic interference from radio transmissions and electric motors can also cause damage or interference and should be avoided BLOWDOWN SOLENOID VALVE COOLING TOWER CIRCULATION PUMP CHILLER MAKE UP WATER METER Throttling device Elec...

Страница 6: ...sed to change the display from one line to the next All menus are circular so when all items in a menu have been displayed the display will return to the originally displayed item ENTER Key Used to access a menu and to log a changed value into the program CLEAR Key Used to clear numerical values from items being changed in the SET UP mode DECIMAL Key Used at certain places to change a function or ...

Страница 7: ...TER key Once you have entered a SET UP sub menu you will be able to step through that menu s options with the down arrow key Relays may be forced on while in the SET UP mode Press the desired relay test key to force it on Press it a second time to turn it off Once the unit returns to the RUN mode relays will activate automatically A Description of SET UP Menu Screens The SET UP menu is the main me...

Страница 8: ...ing the feed time A selectable feed timer can be programmed as one of the following 1 PULSE TIMER A timer activated by dry contacts from a contacting head water meter and includes an accumulator for counting the number of pulse contacts before starting the timer 2 PERCENTAGE A continuously repeating timerwherethecycletimercanbeprogrammed along with the percentage of ON time for the cycle CHEM FEED...

Страница 9: ...two weekdays week and start times and one feed length time and lockout setting for each biocide BIO __ A1 A2 B1 B2 WEEKDAY Select from Sunday through Saturday TuesThrSat MonWedFri Every Other Day Every Day or No Day A setting of No Day disables timer BIO__ A1 A2 B1 B2 WEEK Select week 1 4 Even Weeks Odd Weeks or Every Week A setting of No Week disables timer BIO__ A1 A2 B1 B2 MONTH Select month 1 ...

Страница 10: ...e shown as 13 00 00 CLOCK SET ENTER SET TIME XX XX XX hh mm ss CLEAR To change clock setting ENTER To accept value keyed in using number keys SET DATE XX XX XX CLEAR To change date ENTER To accept value keyed in using number keys SET DAY OF WEEK ENTER To change day of week To cycle through day options ENTER To set day SET WEEK X ENTER To change week To cycle through week options ENTER To set week ...

Страница 11: ...y not apply depending on the controller model but will always be present PASSWORD If a value of 0000 is entered a password is not required If a password is entered it must be used to operate the controller If the first digit is 0 relays may be activated without a password RESET WATER METER COUNT Does not apply unless the unit has selectable feed timer WATER METER IN Select a contacting head water ...

Страница 12: ...Continued FLOW WHEN CLOSED For flow switches FLOW ALARM With FLOW ALARM ON when the system loses flow an alarm signal can be sent FLOW ALARM OFF means that no alarm signal is sent in the event of loss of system flow NO BIOS WITHOUT FLOW Allows the biocide timer s to run only with a flow condition or to ignore the flow and always run even without flow FEED OK WHEN BIO The chemical feed timer can be...

Страница 13: ...o test its function NOTE Pressing the SET UP RUN key returns display to the main menu Pressing ENTER again returns to TEST KEYPAD LEVELS INACTIVE Press ENTER to select between having level alarms active or inactive If level wand are present select inactive Display will flash all spaces should light press ENTER againt to finish test Key on keypad pressed corresponding number appears on display ENTE...

Страница 14: ...eshooting The Advantage Microtron controller is designed for many years of trouble free operation Should a problem occur refer to the following chart to help identify the problem SYMPTOM POSSIBLE CAUSE SOLUTION No system power Power source Check power source Cable from power supply Secure cable board to relay board No output power Check relay fuse Replace as needed Check ribbon cable from Secure r...

Страница 15: ...and provide our technician with Model and Serial Number information If he is unable to diagnose and solve your problem over the phone a fully warranted replacement unit will be shipped usually within 48 hours on a 30 Day Billing Memo This service requires a purchase order and the replacement unit will be billed at current list price for that model less any applicable resale discount Upon return of...

Страница 16: ... treatment equipment needs Cooling Tower Controllers Boiler Blow Down Controllers Blow Down Valve Packages Solenoid Valves Water Meters Chemical Metering Pumps Corrosion Coupon Racks Chemical Solution Tanks Solid Feed Systems Feed Timers Liquid Level Controllers Glycol Feed Systems Pre Fabricated Systems 4 Get the Advantage 11 500 CONDUCTIVITY uS cm ...

Отзывы: