MODBUS REGISTERS
Register Coil
Use
Range Units
Notes
Temperature Setpoint
1
R/W
0-250
F
From Process Temperature
7
R
0-255
F
To Process Flow Rate
8
R
0-99
GPM
Process Status
9
1-16
R
Machine Status 1
10
17-32
R
Machine Status 2
11
33-48
R
Process Status No Alarm*
12
49-64
R
Machine Status 1 No Alarm*
13
65-80
R
Machine Status 2 No Alarm*
14
81-96
R
Heartbeat-On Then Off
15
97-112 R
Machine Control
16
113-128 R
* These registers are mirrors of 9-11. They are used to indicate errors without sounding an alarm. They can be used to indicate when a problem is present
even when the alarm is shut off.
•• These bits will activate when the temperature is outside of the range set by the setoint and the deviation. This doesn not indicate an error.
Pump
Press
Flow
Phase
Wrong
Heater
Flow
16
Notes:
IP Address 200.0.0.203 (typical)
Subnet Mask 255.255.255.0
Gateway none
Protocol RTU
Address 1
Baud Rate 9600
Temperature Setpoint 2
2
R/W
0-250
F
2nd Setpoint
Temperature High Alarm
3
R/W
0-50
F
Deviation Value
Temperature Low Alarm
4
R/W
0-50
F
Deviation Value
Flow Low Alarm
5
R/W
0-99
GPM
Deviation Value
To Process Temperature
6
R
0-255
F