Portable Chiller: MGD-15W-ADV-02
Page: 25
ADVANTAGE ENGINEERING, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729 Fax: 317-881-1277
Service Department Fax: 317-885-8683
b.
Adjusting the Low Flow Bypass:
The unit is equipped with an automatic low flow bypass valve:
An adjusting stem is located on the top of the valve. Remove the cap
with an adjustable wrench and use a flat head screwdriver to adjust the
valve. Turning the stem in the clockwise direction puts more pressure on
the valve’s spring reducing bypass flow. Turning the stem in the
counterclockwise direction puts less pressure on the spring and
increases bypass flow. If the low-pressure digital display reading is
below normal, reduce the pressure on the spring to provide more
bypass.
Содержание MGD-15W-MGD-ADV-02
Страница 6: ...THIS PAGE INTENTIONALLY BLANK Page 6 ...
Страница 80: ...END 2022 Advantage Engineering Inc RE 20220427 ...