Now set the controller input parameters as follows:
P1 HEAT = 2*P if system was heating in step 2.
P1 HEAT = 4*P if system was cooling in step 2.
I1 HEAT = 1.2*t
D1 HEAT = t/8
P2 COOL = P if system was heating in step 2.
P2 COOL = 2*P if system was cooling in step 2.
I2 COOL = 1.2*t
D2 COOL = t/8
6.0 System Alarms/Troubleshooting
The
ElectraCOOL
LA 550 Chiller has four system alarms that when triggered will
show on the display. When an alarm is displayed the system will not attempt
to heat or cool the coolant and the RED status light will illuminate. The P&ID is
included at the end of this section for your reference.
Tank Level Low:
Liquid reservoir level is too low. This is a warning only
and will not trigger the system failure alarm. It will illuminate the
RED status light.
Unless filling for the first time, check all
outside plumbing lines for leaks. Once all leaks are sealed, follow
the procedure in section 4.2 and add more coolant until the alarm
disappears.
Warning! Always disconnect the DC power cord before
opening the
ElectraCOOL
LA 550 Chiller cover as electrical
shock hazards exist inside.
RTD Open The temperature sensor has failed or its connector has come
loose.
/Shorted:
Turn off the ElectraCOOL LA 550 Chiller and disconnect the DC
power cord. Open the controller panel and check that the 5-pin
connector is firmly attached to the controller board and there are
no loose wires in the white miniature RTD connector located
inside. If both are correct, replace the internal RTD as per the
procedure in section 7.5.
Fan Fail:
Fan is supplying insufficient air to cool the thermoelectrics.
Either
one or both of the fans have failed or the airflow into or out of
the system is blocked. Check that the front and rear air inlet and
outlet gratings are not blocked. The ElectraCOOL LA 550 Chiller
requires at least 6 inches of clearance around these gratings. If
airflow is not blocked, contact ADVANCED THERMOELECTRIC for
an RMA number to return the unit for fan replacement.