47
IN DETAIL
CONDITIONS FOR USEN
Built-in unit (VDE 0160)
EN 50 178
General requirements
EN 60146-1
Design, vertical installation
Operating conditions
EN 60 146-1-1; K. 2.5
Operating location, industry sector
CISPR 6
Temperature behaviour
EN 60 146-1-1; K 2.2
Storage temperature
-25 °C - +55 °C
Transport temperature
-25 °C - +70 °C
Operating temperature
-10 °C - +40 °C
with external cooling (280A)
-10 °C - +45 °C with self air cooling
-10 °C - +55 °C
with reduced type current -2%/°C
Load class
1
EN 60 146-1-1 T.2
Humidity class
F
EN 50 178 Tab. 7
Overvoltage category
ÜIII
EN 50 178 Tab. 3
Degree of pollution
2
EN 50 178 Tab. 2
Air pressure
900 mbar * 1000 m above NN
Safe isolation up to 500 V mains voltage
EN 50 178 Chap. 3
Air and creeping distances according
casing / mains potential > 5.5 mm
to EN 50178 Tab. 2 and 3
casing / control potential > 2.5 mm
mains voltage /contr. potent.
≥
10 mm
interface /contr. Potent. -/-
mains voltages interact 2.5 mm
Test voltage
EN 50 178 Tab. 18
Tests according to
EN 60 146-1-1 4.
EMV noise emission
EN 61000-6-4
Noise suppr. control device
Class A
EN 55011 CISPR 11
EMV noise resistance
EN 61000-6-2
Compatibility level
Class 3
EN 61000-2-4
ESD
8 kV (A)
EN 61000-4
Electromagnetic fields
10 V/m
EN 61000-4
Burst mains lines
2 kV (A)
EN 61000-4-5
control lines
2 kV (A)
Surge mains lines
2 kV unsym. EN 61000-4
1 kV sym.
EN 61000-4
control lines
0,5 kV
Line-conducted
EN 61000-4-6
Содержание Thyro-S 1S H 1 Series
Страница 2: ...2...
Страница 35: ...33 FIG 8 CONECTION DIAGRAM THYRO S 1S H 1...
Страница 36: ...34 FIG 9 CONNECTING DIAGRAM 2X THYRO S 1S H 1...
Страница 37: ...35 FIG 10 CONNECTING DIAGRAM THYRO S 1S H RL1...
Страница 38: ...36 FIG 11 CONNECTING DIAGRAM 2X THYRO S 1S H RL1...
Страница 44: ...42 11 DIMENSIONAL DRAWINGS THYRO S 1S 16H 30H THYRO S 1S 45H 60H...
Страница 45: ...43 THYRO S 1S 100H THYRO S 1S 130H 170H...
Страница 46: ...44 THYRO S 1S 280H...
Страница 50: ......
Страница 51: ......
Страница 52: ......
Страница 54: ......